WO37A Cable Pin-out and Wire Color Coding
DB9F female Connector Wire Color
Pin 2 connects to ........................................... RED
Pin 3 connects to ...................................... GREEN
Pin 4 connects to ..................... WHITE (YELLOW)
Pin 5 connects to ....................................... BLACK
Pins 1, 4, and 6 (DCD, DTR, and DSR) jump together.
Pins 7 & 8 (RTS and CTS) jump together.
Brand & Model Format Baud Rate Maximum Thermostats Required Number of M1XSP and Other Equipment
M1G / M1EZ8 M1 (Std)
RCS TR-16 RS-485 Auto 9600 16 2 1 M1XSP handles all thermostats
RCS TR-40 RS-485 Auto 9600 16 2 1 M1XSP handles all thermostats
RCS TR-16 RS-232 Auto 9600 7 1 RCS 232 format requires 1 M1XSP per Thermostat
Aprilaire 8870 RS-485 Auto 9600 16 2 1 M1XSP + 8811 Adapter & 8818 Dist. Panel required
HAI RC Series RS-232 Auto 300 16 2 1 M1XSP for every 4 thermostats **
** IMPORTANT: When interfacing with HAI Thermostats, address switches on the M1XSP may ONLY be set to 1, 2, 3, or 4.
Address 1 talks with HAI Thermostats addressed as 1 thru 4. Address 2 talks with HAI Thermostats addressed as 5 to 8.
Address 3 talks with HAI Thermostats addressed as 9 to 12. Address 4 talks with HAI Thermostats addressed as 13 to 16.
THERMOSTAT COMPATIBILITY CHART
9 Pin Serial (DB9M male to DB9F female) Cable
The M1 requires only 3 wires to be connected:
Connector Connector
DB9M male Wire Color DB9F female
Pin 2 connects to ............. N/A ........................ Pin 2
Pin 3 connects to ............. N/A ........................ Pin 3
Pin 5 connects to ............. N/A ........................ Pin 5
The M1XSP options are selected by the placement of black shorting plugs onto gold plated jumper pins. Some jumpers have 3 pins with a
selection of "0" or "1". Some Jumpers have only 2 pins with a selection of Off or On. Options vary by manufacturer. See detailed installation and
hookup diagrams and the tables below to select options.
MODE
Jumpers
Serial Port Exp.
RCS Thermostat
HAI Thermostat
Aprilaire Thermostat
OnQ-ALC
PCS-UPB
Centralite
EDT - iLine
Uplink "AnyNET" Radio
[future]
[future]
Insteon
[future]
Dynalite (au)
Lutron Radio RA
WGL W800RF32
Jumper Settings
** (S4 for future use)
S4 S5 S6 S7 S8
- 1 0 0 0
- 1 0 0 1
- 1 0 1 0
- 1 0 1 1
- 1 1 0 0
- 1 1 0 1
- 1 1 1 0
- 1 1 1 1
- 0 0 0 0
- 0 0 0 1
- 0 0 1 0
- 0 * 0 1 1
- 0 1 0 0
- 0 1 0 1
- 0 1 1 0
- 0 1 1 1
Special setup, notes, and comments
BAUD Jumpers must be set to desired speed.
Set JP3 to 232 or 485 depending on RCS model
JP5 must be "ON" for this mode.
JP5 must to "ON" for this Mode
Requires special "dedicated" firmware ver.50.x.x
RS-485 (Command Only - No Status Received)
W800RF32 receives X10 RF devices
NOTE: With the exception of the Insteon Mode, BAUD Jumpers are only required
to be set when the M1XSP is configured as a "Serial Port Expander". See
Insteon instructions for special BAUD settings. The other Mfg. mode settings
preselect the BAUD Speed internally preset. Refer to MODE Jumpers above.
** Jumper S4 is for future expansion use and is shown for reference purposes only. Current production
M1XSPs do not provide this jumper. Jumper S5 was not provided on very early production units. The
equivalent value of position S4 with no jumper is a 1.
* In the Insteon mode S5 has an alternate setting of 1 to allow more X-10 units in lieu of Insteon groups.
Other Jumper Settings
JP1 Used to engage a 120 Ohm resistor for terminating the M1 RS-485 Data Bus. See M1 Data bus wiring instructions before use.
JP2 Used to engage a 120 Ohm resistor for terminating the 'Outbound' (External) RS-485 Data Bus if required by other manufacturer.
JP3 Selects either RS-232 or RS-485 format communications on the 'Outbound' connections. Jumper Left = RS-232, Jumper Right = RS-485
JP4 Not used
JP5 Used to supply +12V to pin 4 (DTR) of the DB9 Female connector for certain modes. This jumper can be left on always.
BAUD Rate
(Preset Speed)
Select from Chart
(9,600)
(300)
(9,600)
(9,600)
(4,800)
(19,200)
(9,600)
(9,600)
* Set Baud Jumpers to 111
(9,600)
(9,600)
(4,800)
Jumper
Settings
S1 S2 S3
0 0 0
1 0 0
0 1 0
1 1 0
0 0 1
1 0 1
0 1 1
1 1 1
BAUD
Rate
110
300
1200
2400
4800
9600
19,200
38,400
THE ABOVE CHART REPRESENTS COMPATIBILITY AS OF FIRMWARE VER. 1.0.14