Installation manual
M1G Installation and Programming
Page 68
† Not evaluated by UL
NOTE: A recent revision to UL985 requires that a minimum 1/4” separation be provided and
maintained between power-limited conductors and non-power-limited conductors.
Because the Battery conductor leads are non-power-limited, we recommend they be
routed in the shortest and most direct path from the Control to the Battery itself, regardless
of the enclosure type of brand. For 28” or larger enclosures, a battery shelf (e.g. ELK-
SWS) may be necessary. Under no circumstances should any “power-limited” conductors
be routed within 1/4” of the non-power-limited battery leads. The best procedure is to
avoid the shaded “KEEP OUT” area entirely, as depicted in these diagrams.
Appendix F - Regulatory Agency Statements (cont)