Installation manual

M1G Installation and Programming
Page 67
Home Health Care (UL 1637) Listed Installations
Requirements described under UL985 plus:
* A minimum of two (2) keypads are required with one keypad powered from “+VKP” and one keypad powered from “+VAUX”.
Commercial - Central Station (UL 1610), Police Station Connected (UL 365), Local Burglar Alarm (UL 609) Listed Installations
Requirements described under UL1023 plus:
* The Alarm Cutoff timer must be set to 00900 sec. (15 min.) or greater.
* UL Commercial Burg requires 4 hours of standby power. Limit combined continuous current draw from terminals +SAUX, +VAUX, +VKP, and
connector J16 to 450 mA max. and use one (1) 8 Ah battery. A supplementary UL Listed, Battery Backed-up Power Supply must be
connected to power additional Keypads and Expanders if the combined continuous current draw from terminals +SAUX, +VAUX, +VKP, and
connector J16 exceeds 450 mA.
* An acceptable Commercial enclosure must be used (see Listed Enclosures below)
* A UL LIsted Tamper Switch(s) must be installed on the enclosure and connected to a 24 hour Burg Tamper defined Zone.
* All Keypads need to be installed within the protected area (they have no tamper)
* DO NOT USE an A B Attack Cabinet for the external sounder
* A Whenever/And/Then rule should be written (using ElkRP software) to enable the Output 2 Siren to ‘chirp’ upon closing ringback.
UL Canada Listed Installations (ULC S304 and ULC S303)
Requirements described under UL1023, 1610 plus:
* The Alarm Cutoff timer must be set to 00900 sec. (15 min.) or greater.
*UL
Canada Commercial Burg requires 24 hours of standby power. Limit combined continuous current draw from terminals +SAUX, +VAUX,
+VKP, and connector J16 is 450 mA max. and use two (2) 8 Ah batteries in parallel.
* Zone Expanders must be in an acceptable Commercial enclosure (see Listed Enclosures below)
* Communications Channel Security Applications: Low Risk, Passive Level 1 (P1), Extent 1 (CAN/ULC-S302)
* For Phone Line Fault, the delay time setting must be for Max. 3 minutes.
* For System Report Codes and Options, the setting must be for Max. 90 seconds for reportiing changes in the status of the control unit,
including alarm, trouble, open and close signals.
Appendix F - Regulatory Agency Statements (cont)
LISTED ENCLOSURES:
For Household Burglar or Household Fire Listed Installations one of the following enclosures must be used:
* ELK 14” Enclosure model ELK-SWB14 or ELK-UB14
* ELK 28” Enclosure model ELK-SWB28
* OnQ Legrand 14” Enclosure models 363474-01or 363474-11 utilizing the Universal Mounting plate part no. 364453. Not LISTED FOR CANADA
* OnQ Legrand 28” Enclosure models 363475-01, 363475-11, 364591-01, 364591-02 or364591-11 utilizing the Universal Mounting plate part no.
364453. Not LISTED FOR CANADA
* OnQ Legrand 42” Enclosure models 363476-01,363476-11,364592-01, 364592-02, or 364592-11 utilizing the Universal Mounting plate part no.
364453. Not LISTED FOR CANADA
For Commercial Listed Installations the following enclosure must be used:
* ELK-TB14 Tamper Resistant Enclosure
SUPPLEMENTARY POWER SUPPLY:
UL Listed, Class 2
Plug-in Transformer
as called out by the
Power Supply Mfg.
RED
This diagram shows how to properly connect a Supplementary UL Listed, Battery Backed-up Power Supply when the
combined total current draw from the control is more than the allowable current as per the UL requirements.
WHITE
GREEN
ELK-M1
RS-485 DATA BUS
BLACK
Connect Negatives of both
supplies together.
** The battery on the supplementary power supply will be supplying power during a power outage to the Data Bus Devices connected to it. The Power Supply and
backup Battery should be sized to supply the UL required minimum standby time according to the Data Bus Devices e.g. Keypads, Expanders connected.
UL Listed,
Battery Backed-up
Power Supply
+VKP
NEG
DATA B
DATA A
AC AC + BAT - + DC -
Rechargeable
Stand-by Battery
**
RED
WHITE
GREEN
BLACK
BLACK
Data Bus Devices e.g.
Keypads, Expanders
Data Bus Devices e.g.
Keypads, Expanders