M1G Installation and Programming
Page 53
† VOICE -
This section is used to setup and customize many of the 6 word phrases that can be spoken by the control
during a certain event or when commanded by an automation rule. The capabilities of this section are quite powerful. The
library contains over 500+ words in addition to specialized speech commands for inserting conditions, current time, status/
state, time delays, and even an 800hz tone. In addition, any of the 10 custom recordable messages can be included when
building these 6 word phrases.
CUSTOM SETTINGS - These are 20 memory locations which may be assigned a 12 character description, a function type
(one of 3), and a starting value. An authorized user can then access the custom settings from keypad user menu 7-
Automation Custom Settings, and modify the value whether it be a numeric value, a timer (seconds), or a time-of-day.
Incorporating custom settings in rules provides the user the ability to modify how the rule will operate. For instance, the user
can modify the time or duration for the lawn sprinklers which have been programmed to turn on automatically. The function
types include: A 5 digit raw number with a range of 00000 to 65,535, a 5 digit timer (seconds) with a range of 00000 to 65,535
seconds, or a Time (time of day) which is formatted as 00:00 with a range of 00:00 to 23:59.
COUNTERS - These memory locations (often called flags) can be set, incremented, decremented, or compared by an
automation rule to track an event or keep up with how many times an event has occurred. There are a total of 64 counters.
Each can be programmed with a 12 character description, making it easy to reference in an automation rule.