Installation manual

M1G Installation and Programming
Page 42
Z001: Selb Prgr
[Name of Zone]
Z001:A=00 R=00 r
Byp=00 Tbl=00
Menu 10 - Zone Reporting Codes
10-Zone Reportng
Codes r
Zone Report Codes Description of Option
Each of the 208 Zones has specific communicator reporting codes for Alarm, Restore,
Bypass, and Trouble. Using the up/down arrow keys, select the appropriate zone, then
press the right arrow key to begin programming of that zone.
The cursor starts at the 00 beside A (Alarm). Enter the desired two digit reporting code
and press the right arrow key to advance to the R (Restore). To jump the cursor to another
report without changing this one simply press the right arrow key. The next press of the
right arrow key after Tbl (Trouble) will advance the screen back to the beginning of that
zone. Range is 00 to FF. Default for all entries is 00 (no report).
NOTE: Each reporting code must be programmed according to the desired reporting
format. However, for SIA and Contact ID formats the actual reporting digits will be
produced by the control according to the type of alarm or event. The only programming
required to enable reporting with the SIA and Contact ID formats is to set the programmed
code to a non zero (0) value. See below:
Press RIGHT arrow key to select this menu. Press UP or DOWN arrow keys to select
another menu. The ELK key backs up one menu level. To exit press the * or Exit key.
NOTE: Enter a two digit value to enable a report code. To disable a report code enter 00. When SIA or Contact ID is the
reporting format, the two digit value can simply be 01 since the control automatically produces the correct code
according to the SIA or Contact ID protocol. For 4+2 pulse format, enter a value from 01 to FF. To enter the A thru F
HEX characters press the RIGHT arrow key to position the cursor under the desired digit, then press the UP arrow (shift)
key once. Each press of the 2 key will now produce the following: 2, A, B, C. Each press of the 3 key will now produce
the following: 3, D, E, F. Press the RIGHT arrow key to cancel shift and move to the next character. See Appendix for
a summary of the SIA and Contact ID codes.
Alarms Restore Bypass Trouble
Zone RCs CID SIA CID SIA CID SIA CID SIA
01 = Burglar Entry/Exit 1 134 BA 134 B R 573 BB 370 BT
02 = Burglar Entry/Exit 2 134 BA 134 B R 573 BB 370 BT
03 = Burglar Perim Inst 131 BA 131 B R 573 BB 370 BT
04 = Burglar Interior 132 BA 132 B R 573 BB 370 BT
05 = Burglar Int Follower 132 BA 132 B R 573 BB 370 BT
06 = Burglar Int Night 135 BA 135 B R 573 BB 370 BT
07 = Burglar Int Nt Fllwr 135 BA 135 B R 573 BB 370 BT
08 = Burglar 24 Hour 133 BA 133 B R 573 BB 370 BT
09 = Burglar Box Tamper 137 TA 137 T R 573 TB 370 BT
10 = Fire Alarm 110 FA 110 F R 571 FB 373 FT
11 = Fire Verified 110 FA 110 F R 571 FB 373 FT
12 = Fire Supervisory 200 FS 200 F R 571 FB 373 FT
13 = Aux Function 1 150 UA 150 U R 572 UB ---- ----
14 = Aux Function 2 150 UA 150 U R 572 UB ---- ----
15 = Keyfob ---- ---- ---- ---- ---- ---- ---- ----
16 = Non Alarm ---- ---- ---- ---- ---- ---- ---- ----
17 = Carbon Monoxide 162 GA 162 GR 572 GB ---- ----
Based on the zone definition, the CID (Contact ID) or SIA formats for Zone Reporting Codes will be:
Alarms Restore Bypass Trouble
Zone RCs CID SIA CID SIA CID SIA CID SIA
18 = Emergency Alarm 101 QA 101 Q R 572 QB ---- ----
19 = Freeze Alarm 159 Z A 159 Z R 572 ZB ---- ----
20 = Gas Alarm 151 GA 151 G R 572 GB ---- ----
21 = Heat Alarm 114 KA 114 K R 572 KB ---- ----
22 = Medical Alarm 100 MA 100 M R 572 MB ---- ----
23 = Police Alarm 120 P A 120 P H 572 PB ---- ----
24 = Police No Indication 120 P A 120 H H 572 PB ---- ----
25 = Water Alarm 154 WA 154 WR 572 WB ---- ----
26 = Key Mom Arm/Disarm ---- ---- ---- ---- ---- ---- ---- ----
27 = Key Mom Arm Away ---- ---- ---- ---- ---- ---- ---- ----
28 = Key Mom Arm Stay ---- ---- ---- ---- ---- ---- ---- ----
29 = Key Mom Disarm ---- ---- ---- ---- ---- ---- ---- ----
30 = Key On/Off ---- ---- ---- ---- ---- ---- ---- ----
31 = Mute Audibles ---- ---- ---- ---- ---- ---- ---- ----
32 = Power Supervisory 338 YT 338 YR 572 UB ---- ----
33 = Temperature ---- ---- ---- ---- ---- ---- ---- ----
34 = Analog Zone ---- ---- ---- ---- ---- ---- ---- ----
NOTE: On CID reporting the 3 digit code is preceded by a “1” for new events or a “3” for restore (previous reported) events.