Installation manual
M1G Installation and Programming
Page 26
A1: Selb Prgr
Area 1
A1 01:=060 r
Exit Delay1 Time
A1 02:=030 r
Entry Delay1Time
A1 03:=060 r
Exit Delay2 Time
A1 04:=030 r
Entry Delay2Time
A1 05:=No r
AutoStay No Exit
Menu 03 - Area Definitions
Of the 8 potential areas (partitions), Area 1 is the first to display. Press the right arrow
key to program, or press the up or down arrow keys to select another area. To jump to a
specific area enter the number (1-8). The area name is displayed on the bottom.
The amount of exit time in seconds for all zones programmed as Exit Delay 1. Range is
045 to 255 seconds. Default value is 060. If an Exit Delay 1 zone is enabled for force
arm, its exit time will be the greater of the values for Exit 1 or Exit 2. Do not
enable force arm on Exit Delay 1 zones if this operation is not desired.
The amount of entry delay time in seconds for zones programmed as Entry Delay 1.
Range is 030 to 255 seconds. Default value is 030.
The amount of exit delay time in seconds for zones programmed as Exit Delay 2. Range
is 045 to 255 seconds. Default value is 060. See note above regarding force arm
and Exit Delay 1 zones.
The amount of entry delay time in seconds for zones programmed as Entry Delay 2.
Range is 030 to 255 seconds. Default value is 030.
If Yes, the control will switch from AWAY mode to STAY mode at the end of the exit delay
time if no exit zone is violated (no exit detected). NOTE: This tracks the longest of the
two exit timers. All interior zones are bypassed in the STAY mode. Default value is No.
†† If this option is set to Yes (default), the exit procedures will be affected in three ways:
A1 06:=Yes r
Exit1TimeRestart
03-Area r
Definitions
Area Defintions Description of Option
Press RIGHT arrow key to select this menu. Press UP or DOWN arrow keys to select
another menu. The ELK key backs up one menu level. To exit press the * or Exit key.
1)
Additional Exit1 “Grace” feature - During the initial Exit Delay 1 time if the zone violates a second time and restores,
the exit timer will automatically restart one time. I.E. If the Exit1 door is opened, closed, and then opened again the
timer will restart. NOTE: This only works on Exit Delay 1 zones and the timer only restarts one time. It does
NOT work if the zone is enabled for force arm! This features complies with the SIA CP-01. †
2) “Leave for Work” or “Pet” feature - When armed in one of the Stay modes a User may press the Exit key to re-start
the exit delay in order to open an exit/entry door and leave for work. The system remains in the Stay mode in case
other family members are still in the house. This can also be used to let a pet outdoors. When the pet is ready to
come back inside the User can press the Exit key again to restart the timer and open the door.
3) Going from Stay to Away Mode - When armed in one of the Stay modes a User may change the arm mode to Away
by pressing the Exit key twice in short succession (within 3 seconds) and the leave the building.
Exit Error If an entry/exit zone is violated when the Exit Delay expires, the Exit Error Feature will be activated. The
local siren will sound immediately and the Entry Delay warning will begin. IF the control is not disarmed before the
delay expires the communicator will report the alarm along with an Exit Error code, provided these codes are
programmed. An Exit Error event flag will also be set which can be used by the “Whenever/And/Then” rules (refer to
the ELK-RP software) to sound a siren, or blink a light, or whatever. Exit Error complies with SIA CP-01. †
† Not evaluated by UL †† Not for use in UL Listed Systems