User's Manual
M1 Installation and Programming Manual
Page 45
SR14: T=00 R=00 r
Phone Line Fault
SR15: T=00 R=00 r
Output 2 Trouble
SR13: 00= Up/ r
Download End
Low Battery T (Trouble) will be reported if the battery drops below 11.2 Volts. Low Battery
R (Restore) will be eligible to report once the battery has passed a test at 11.5 Volts or
higher. Range is 00 to FF. Default is 00 (no report).
Memory Error T (Trouble) will be reported if the system memory checksum fails. An
upload or review of the programming is the only way to detect where the error occurred.
To clear the error and send a R (Restore) you must enter and exit the installer
programming mode. Range is 00 to FF. Default is 00 (no report).
Up/Download End will be reported upon completion of a Up/Download session as a
verification that the control was accessed. Range is 00 to FF. Default is 00 (no report).
Phone Line Fault T (Trouble) will be reported if the Voltage and Current is lost on the
telephone line. Phone Line Fault R (Restore) will report upon restoral of the telephone
line. Range is 00 to FF. Default is 00 (no report).
Output 2 T (Trouble) will be reported if an open circuit occurs on Output 2. Output 2 R
(Restore) will be reported upon restoral of the connection. Range is 00 to FF. Default is
00 (no report).
Menu 12 - Sys Report Code Options & Codes (continued)
Sys Rpt Code Options Description of Option
SR11: T=00 R=00 r
Low Battery
SR12: T=00 R=00 r
Memory Error
System RCs CID SIA
AC Fail 1301 A T
AC Restore 3301 A R
Automatic Test 1602 R P
Aux Over Current 1312 Y P
Aux Over Current Restore 3312 Y Q
Expansion Module Trouble 1333 E T
Expansion Module Restore 3333 E R
Local Programming Begin 1627 L B
Local Programming End 1628 L X
System RCs CID SIA
Log 80% Full 1623 J L
Low Backup Battery 1302 Y T
Low Battery Restore 3302 Y R
Memory Error 1304 Y F
Remote Programming End 1412 R S
Telephone Line Fault 1351 L T
Telephone Line Restore 3351 L R
Output 2 Trouble 1322 Y A
Output 2 Restore 3322 Y H
Based on the event, the CID (Contact ID) or SIA Codes for System Reporting Codes will be: