User's Manual

M1 Installation and Programming Manual
Page 31
ZN001 02:Type=0r
0=EOL Supervised
ZN001 03:Area=1 r
[Area Name]
“Type” refers to the wiring configuration for zones. For Burglar and Keyswitch zones the
valid types are: 0=EOL Supervised, 1=Normally Closed, 2=Normally Open, 3=EOL
Security (Day) Alert on Open, or 4=EOL Security (Day) Alert on Short. For ALL other non-
fire zones the types may be 0, 1 or 2 only. Fire zone valid types are: 5=EOL Supervised 4-
wire detectors, 6=EOL Supervised 2-wire detectors (zone 16 ONLY!)
Enter the area (partition) number that this zone is to be assigned to. A zone can only
reside in one area and fire zones can only reside in Area 1.
A zone programmed ‘Yes’ for Silent Alarm will not cause any audible alarm event from a
programmable output OR from any keypad. However, a visual display will occur on the
keypad(s) which are assigned to the same area as the zone.
Menu 05 - Zone Definitions (continued)
15 Keyfob - Used when a wireless keyfob is enrolled into a receiver at this zone ID location.
16 No Alarm - Intended for use in Whenever/And/Then rules from the Remote Programming RP software. This zone
type DOES NOT ACTIVATE any alarm and is not logged in the Event log. No reset is required.
17 Carbon Monoxide 24 hr - Activates an immediate Carbon Monoxide alarm if tripped anytime (armed or disarmed).
The keypad will display the alarm as well as the event log. This type of alarm can be silenced/reset with a valid
User Code. The audible alarm can be set in “Cutoff Timers”.
18 Emergency 24 hr - Similar to Def 17, this zone creates an alarm if tripped anytime (armed or disarmed).
19 Freeze Alarm 24 hr - Similar to Def 17, this zone creates an alarm if tripped anytime (armed or disarmed).
20 Gas Alarm 24 hr - Similar to Def 17, this zone creates an alarm if tripped anytime (armed or disarmed).
21 Heat Alarm 24 hr - Similar to Def 17, this zone creates an alarm if tripped anytime (armed or disarmed).
22 Medical Alarm 24 hr - Activates an immediate Medical alarm if tripped anytime (armed or disarmed).
23 Police Alarm w/Indication 24 hr - Activates an audible Police (Holdup) alarm if tripped (armed or disarmed).
24 Police Alarm no Indication 24 hr - Activates an non-audible Police (Silent) alarm if tripped (armed or disarmed).
25 Water Alarm 24 hr - Activates an immediate Water alarm if tripped anytime (armed or disarmed).
26 Keyswitch Momentary - Intended for a spring loaded momentary key switch. Toggles the armed state (disarmed/
armed) with each trip.
27 Keyswitch Momentary - Away Mode - Intended for a spring loaded momentary key switch. Arms the area in the
AWAY mode with each trip.
28 Keyswitch Momentary - Stay Mode - Intended for a spring loaded momentary key switch. Arms the area in the
STAY mode with each trip.
29 Keyswitch Momentary - Disarm Only - For a spring loaded momentary key switch. Disarms with each trip.
30 Keyswitch On/Off (Maintained) - Intended for a 2 position On/Off key switch. Arms the area in Open position.
Disarms the area in the Closed position.
31 Mute All Area Audibles - For silencing all area audibles by a two-way listen-in module (other manufacturer).
32 Power Supervisory 24 hr - For supervising an external power supply which provides alarm/trouble contacts. Wire
the power supply contacts to short the zone in a Low Battery event and open the zone in an AC Failure event.
33 Temperature - For use with ELK-M1ZTS Temperature Sensors. Requires the use of Whenever/And/Then rules
from the ELK-RP software. NOTE: This definition is for ZONES 1 thru 16 ONLY! Temperature zones must be set
to FAST LOOP (less that 200ms) response.
34 Analog - For sensors that produce a variable voltage (0 to 12 volt range). Requires the Whenever/And/Then rules
from the ELK-RP software. NOTE: This definition is only available with the ELK-M1G (Gold) control.
Def Zone Description Operating Characteristics
0 EOL Supervised, 2,200 Ohm resistor (Zones 1 - 16 are defaulted to Hwd 0)
1 Normally Closed only. No resistor required.
2 Normally Open only. No resistor required.
3 EOL Supervised with Security (Day) Alert on Open. (Burglar & Keyswitch Zones Only) If zone wiring is OPENED
while the control is disarmed the Keypad will beep and display the zone name. Ideal for gun cabinets, exit doors,
etc. Press the Star key to silence beep. User code is required to acknowledge/reset the alert. A regular alarm is
created if the control is armed. Requires the Whenever/And/Then rules from RP software for additional output.
4 EOL Supervised with Security Day Alert on Short. (Burglar & Keyswitch Zones Only) Same as type 3 except the
zone wiring must be SHORTED while the control is disarmed to create the alert. Pressing the Star key silences. A
User code is required to acknowledge/reset the alert. A regular alarm is created if the control is armed. Requires
the Whenever/And/Then rules from RP software for additional output.
5 Fire, 4-Wire Smoke Detector with 2,200 Ohm EOL resistor. Trouble on open, alarm on short. (Zones 1 to 16).
6 Fire, 2-wire Smoke Detector with 680 Ohm EOL resistor. (ZONE 16 ONLY)
Type Wiring Configuration Operating Description
ZN001 04: =No r
Silent Alarm