Installation Manual Gas Fires Summum 100
APPENDICES
27
F CALCULATION TABLE FLUE GAS REDUCTION
The calculation table shows when you need to place a flue gas
ristrictor
Result Action
√ No ristrictor required
R Position the resitrictor
X No good operation guaranteed *
F.1 Horizontal terminal flue diameter F.2 Vertical terminal flue diameter
For a vertical terminal the minimal starting length is 0,5 meter
and the minimal vertical section is 1 meter.
* Perhaps the powerfan is a good solution here.
Total vertical Section
22 √ X X X X X X X X
21 R R √ X X X X X X
20 R R √ √ X X X X X
19 R R R R √ X X X X
18 R R R R R √ √ X X
17 R R R R R R R √ √
16 R R R R R R R R √
15 R R R R R R R R √
14 R R R R R R R R √
13 R R R R R R R R √
12 R R R R R R R R √
11 R R R R R R R R √
10 R R R R R R R R √
9 R R R R R R R R √
8 R R R R R R R R √
7 R R R R R √ √ √ √
6 R R R R R √ √ √ √
5 R R R R R √ √ √ √
4 R R R R R √ √ √ √
3.5 R R R R R √ √ √ √
3 √ √ √ √ √ √ √ √ √
2.5 √ √ √ √ √ √ √ √ X
2 √ √ √ √ √ √ √ X X
1.5 √ √ √ √ √ √ X X X
1 √ √ √ √ √ X X X X
0 0,5 1 2 2.5 3.5 4 4.5 5
Total Horizontal Section
Total vertical Section
10 R R R R R R R √ √
9 R R R R R R R √ √
8 R R R R R R R √ √
7 R R R R R R R √ √
6 R R R R R R R √ √
5 R R R R R R R √ √
4 R R R R R R R √ √
3.5 R R R R R R R √ √
3 √ √ √ √ √ √ √ √ √
2.5 √ √ √ √ √ √ √ √ X
2 √ √ √ √ √ √ √ X X
1.5 √ √ √ √ √ √ X X X
1 √ √ √ √ √ X X X X
0.5 X √ √ X X X X X X
0 0.5 1 2 2.5 3.5 4 4.5 5
Total Horizontal Section