Installation Manual Sky Series EN

12
INSTALLATION MANUAL
7 ATTENTION POINTS GAS FLUE
To guarantee the fire safety regarding you flue gas configuration
a casing is necessary. For this case non-combustible materials
should be used. Make sure to ventilate a sha and never to
insulate it, to make sure the hot air is able to get away.
Every transit or terminal should be made such, that the warmth-
insulation and non-combustability is guaranteed, according to
the building regulation.
7.1 Installation of flue material
Follow the following instrucions for the installation of flue
materials;
Drill a hole of 160 mm for the wall or roof transit with a 150
mm diameter flue connection, and 210 mm with a flue with
a diameter of 200 m.
Keep a distance of at least 50 mm between the outside of
the concentric pipes and the wall or ceiling.
Provide a (fire) safe transit construction in wall, floor or roof
sheeting
Build the system from the fireplace.
Assemble pipes in the correct direction! The inner pipe goes
into and the outer pipe goes over the fireplace connection.
Make sure the tubes are suiciently braced, so the weight of
the tubes are not supported on the hearth.
The concentric pipes could come loose due to expansion
and cooling down. It is recommended that a chuck parker
be used in places that are inaccessible aer installation.
The horizontal drain portion must be fitted sloping to the
hearth.
7.1.1 Adapting the length of the chimney
Not all parts can be adjusted! To fit the drainage system
correctly, you are to use an adjustable fitting. You can use an
adjustable concentric pipe, wall or roof fitting. To get a sealed
flue gasconnection, the inner pipe must always be 2 cm longer
than the outer pipe. Always attach adjustable parts with a chuck.
7.1.2 Calculate chimney
For proper operation of the fireplace it is important that the flue
pipe meets the requirements. Do determine this, we prepared a
calculation chart. (See APPENDIX E & F)