Installation Manual Gas Fires Modore 185
APPENDICES
25
D.2 Terminal location with Horizontal exhaust (C31)
Position terminal dist.
(mm)
A* Directly below an opening, ventilation stone,
casement window etc.
600
B
Above an opening, ventilation stone, casement
window etc.
300
C
In addition to an opening, ventilation stone,
casement window etc.
400
D Under gutters or drain pipes 300
E Under eaves 300
F Under balconies or roofs of open garages 600
G From a vertical drain pipe 300
H
From an inside or outside corner 600
I Above ground roof or balcony level 300
J From a surface opposite the tip 600
K From an end opposite the tip 600
L
From an opening in the open garage (eg door,
window in the house)
1200
M Vertically from one end to the same wall 1500
N Horizontally from one end to the same wall 300
P From a vertical structure on the roof 600
Q Above the intersection with the roof 150
D LOCATION TERMINAL
D.1 Terminal location with vertical exhaust (C11)
Distance Exhaust 1,2 of 3
At the same roof level > 6m *
At a different roof level > 3m * & **
On a lower wall > 2m *
On a higher sloping surface > 6m ***
“Distance” = minimum distance required to position the exhaust
in order to prevent adverse eects in relation to;
1. A ventilation opening of a used room, toilet or bathroom
2. Supply of heated air when the supply flows through a used
room.
3. A window that can be opened and located in the vicinity of
a used room, toilet or bathroom.
* If the required distance is not feasible, the rules regarding the exit
position have priority.
** If the exhaust is placed at least one meter higher than the inlet
opening, or a window that can be opened.
*** If the required distance is not feasible, the exhaust must be placed at
least one meter above the highest façade / roof.
(4) The terminal may not be placed closer than 300 mm to an opening in
the building such as a window frame.
P
Q
Q
Q
C
D,E
A
B
J
J
F
I
Q
N
M
K
H
H
Figure D.1 - Terminal Location