PSB 9000 2.5 kW Series
3.11.16.8 Possible reasons for battery test stop
Thebatterytestfunctionruncanbestoppedbydi󰀨erentreasons:
• Manual stop on the HMI with button STOP
• After the max. test time has been reached and action “End of test” was set for it
• After the max. battery capacity to consume has been reached and action “End of test” was set for it
• Anydevicealarmwhichwouldalsoswitcho󰀨theDCinput,likeOT
• Reaching the threshold U
DV
(discharge voltage)
• Reaching the threshold for charging end current
When the dynamic is running, some of the above items, such as “Reaching threshold U
DV
” will
only stop the currently running test part, i. e. charging or discharging, but not the full test. The
test would then immediately continue with the next part, if at least one is still to proceed.