User Manual
Page 77
EA Elektro-Automatik GmbH
Helmholtzstr. 31-37 • 41747 Viersen
Germany
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
www.elektroautomatik.de
ea1974@elektroautomatik.de
PSB 9000 2.5 kW Series
3.11.15.4 Simulation mode
Apart from the panel technology there is also a simulation mode to select. Four options:
Mode U/I Controllable simulation. Voltage (U
MPP
, in V) and current (I
MPP
, in A) in the maximum power point
(MPP) are variable during runtime. The purpose of this mode is to directly shift the MPP into
various directions.
Mode E/T Controllable simulation. During runtime, the irradiation (E from german “Einstrahlung”, in W/
m²) and surface temperature (T, in °C) of the simulated solar panel are adjustable. This also
impacts the curve and the resulting MPP. The purpose of this mode is to analyse the impact of
temperature and/or irradiation on the performance of a solar panel.
Mode DAY U/I Automaticsimulationrun,processingadaytrendcurveconsistingofupto100,000pointsdened
by values for U
MPP
, I
MPP
and time.
Mode DAY E/T Automaticsimulationrun,processingadaytrendcurveconsistingofupto100,000pointsdened
by values for irradiation, temperature and time.
3.11.15.5 Day trend
The so-called day trend is a special simulation mode for long-term tests. It processes a curve consisting of up to
100,000user-denablepoints.Foreveryprocessedpointonthatcurve,thePVcurveiscalculatedanew.
Everypointisdenedby3valuesofwhichoneisthedwelltime.Whendeninglongdwelltimesthedaytrend
curve can be supported by an interpolation feature which can be optionally activated. It will calculate and set in-
termediate points between two succeeding curve points. Hence it should be considered to run the day trend with
or without interpolation.
Thedaycurvepointshavetobeloadedintothedevice,eitherfromaCSVleonUSBstickorviadigitalinterface.
The user selects the number of points according to the requirements of the simulation.
FormatsoftheCSVlestoloadfromUSBstickwhenmanuallyconguringthefunction:
• For Mode DAY E/T(requiredlenameformat:PV_DAY_ET_<arbitrary_text>.csv)
Column A = Index
Anascendingnumberbetween1and100,000(therstempty
index will cause the simulation to stop)
Column B = Irradiation (E) in W/m²
Allowed range: 0...1500
Column C = Temperature (T) in °C
Allowed range: -40...80
Column D = Dwell time in milliseconds (ms)
Allowed range: 500...1.800.000
• For Mode DAY U/I(requiredlenameformat:PV_DAY_UI_<arbitrary_text>.csv)
Attention! The values in columns B and C are real values which must not exceed the ratings of
thedeviceorthedevicewillneglecttoloadthele.
Column A = Index
Anascendingnumberbetween1and100,000(therstempty
index will cause the simulation to stop)
Column B = Voltage U
MPP
in V
Allowed range: 0...rated output voltage of the device
Column C = Current I
MPP
in A
Allowed range: 0...rated output current of the device
Column D = Dwell time in milliseconds (ms)
Allowed range: 500...1.800.000
The number format and the column separator in the CSV les is determined by the regional
settings of the PC or the software used to create the les. The format must match the selection
for the device setting “USB le separator format” in the General Settings menu of the device,
else the device would neglect loading the le. For example, an american Excel should by default
use the dot as decimal separator and the comma as column separator, which would match the
selection “USB le separator format = US”.