User Manual

Page 44
EA Elektro-Automatik GmbH
Helmholtzstr. 31-37 • 41747 Viersen
Germany
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
www.elektroautomatik.de
ea1974@elektroautomatik.de
PSB 9000 2.5 kW Series
IF Level 1 Description
Probus DP
Node Address
SelectionoftheProbusornodeaddressofthedevicewithinrange1...125viadirectinput
Function Tag
Stringinputboxforauser-denabletextwhichdescribestheProbusslavefunctiontag.
Max. length: 32 characters
Location Tag
Stringinputboxforauser-denabletextwhichdescribestheProbusslavelocationtag.
Max. length: 22 characters
Installation Date
Stringinputboxforauser-denabletextwhichdescribestheProbusslaveinstallation
date tag. Max. length: 40 characters
Description
Stringinputboxforauser-denabletextwhichdescribestheProbusslave.
Max. length: 54 characters
IF Level 1 Level 2 Level 3 Description
Ethernet / ModBus-TCP, 1 & 2 Port
IP Settings 1 DHCP The IF allows a DHCP server to allocate an IP address, a subnet
mask and a gateway. If no DHCP server is in the network then
networkparameterswillbesetasdenedinitem“Manual”
Manual IP address This option is activated by default. An IP address can be man-
ually allocated.
Gateway Here a gateway address can be allocated if required..
Subnet mask Hereasubnetmaskcanbedenedifthedefaultsubnetmask
isn’t suitable.
DNS address 1
DNS address 2
HeretheaddressesoftherstandsecondDomainNameServ-
ers(DNS)canbedened,ifneeded.
Port Range: 0...65535. Default ports:
5025 = Modbus RTU (all Ethernet interfaces)
Reserved ports which must not be set with this parameter:
502 = Modbus TCP (Modbus-TCP interface only)
other typical reserved ports
IP Settings 2-P1
IP Settings 2-P2
AUTO Settings for the Ethernet port such as transmission speed are
set automatically.
Manual Half duplex Manual selection for transmission speed (10MBit/100MBit) and
duplex mode (full/half). It’s recommended to use the “AUTO”
option and only revert to “Manual” if these parameters fail. Dif-
ferent Ethernet port settings for 2-port modules are possible, as
these include an Ethernet switch
Full duplex
10MBit
100MBit
Host name Free choice of host name (default: Client)
Domain name Free choice of Domain (default: Workgroup)
TCP Keep-Alive Enable TCP keep-alive
IF Level 1 Description
Pronet/IO, 1 & 2 Port
Host name
Free choice of host name (default: Client)
Domain name
Free choice of Domain (default: Workgroup)
Function Tag
Stringinputboxforauser-denabletextwhichdescribesthePronetslavefunctiontag.
Max. length: 32 characters
Location Tag
Stringinputboxforauser-denabletextwhichdescribesthePronetslavelocationtag.
Max. length: 22 characters
Station Name
Stringinputboxforauser-denabletextwhichdescribesthePronetstationname.Max.
length: 200 characters
Description
Stringinputboxforauser-denabletextwhichdescribestheProbusslave.Max.
length: 54 characters
Installation Date
Stringinputboxforauser-denabletextwhichdescribestheProbusslaveinstallation
date tag. Max. length: 40 characters