Elektro-Automatik Operating Guide PSB 9000 2.
PSB 9000 2.5 kW Series TABLE OF CONTENTS 1 GENERAL 1.1 1.1.1 1.1.2 1.1.3 1.1.4 1.2 1.3 1.4 1.5 1.6 1.7 1.7.1 1.7.2 1.7.3 1.7.4 1.7.5 1.8 1.8.1 1.8.2 1.8.3 1.8.4 1.8.5 1.9 1.9.1 1.9.2 1.9.3 1.9.4 1.9.5 1.9.6 1.9.7 1.9.8 1.9.9 1.9.10 1.9.11 1.9.12 1.9.13 2 About this document.......................................5 Retention and use...........................................5 Copyright.........................................................5 Validity......................................................
PSB 9000 2.5 kW Series 3.7.2 3.8 3.9 3.10 3.11 3.11.1 3.11.2 3.11.3 3.11.4 3.11.5 3.11.6 3.11.7 3.11.8 3.11.9 3.11.10 3.11.11 3.11.12 3.11.13 3.11.14 3.11.15 Device alarm and event handling.................57 Control panel (HMI) lock...............................59 Limits lock......................................................60 Loading and saving a user profile................60 The function generator.................................61 Introduction...................................................
PSB 9000 2.5 kW Series 1. General 1.1 About this document 1.1.1 Retention and use This document is to be kept in the vicinity of the equipment for future reference and explanation of the operation of the device. This document is to be delivered and kept with the equipment in case of change of location and/or user. 1.1.2 Copyright Reprinting, copying, also partially, usage for other purposes as foreseen of this manual are forbidden and breach may lead to legal process. 1.1.
PSB 9000 2.5 kW Series 1.4 Disposal of equipment 1.5 Product key A piece of equipment which is intended for disposal must, according to European laws and regulations (ElektroG, WEEE) be returned to the manufacturer for scrapping, unless the person operating the piece of equipment or another, delegated person is conducting the disposal.
PSB 9000 2.5 kW Series 1.7 Safety 1.7.1 Safety notices Mortal danger - Hazardous voltage • Electrical equipment operation means that some parts can be under dangerous voltage. Therefore all parts under voltage must be covered! This basically applies to all models, though 60 V models according to SELV can’t generate hazardous DC voltage.
PSB 9000 2.5 kW Series 1.7.2 Responsibility of the user The equipment is in industrial operation. Therefore the operators are governed by the legal safety regulations. Alongside the warning and safety notices in this manual the relevant safety, accident prevention and environmental regulations must also be applied.
PSB 9000 2.5 kW Series 1.7.5 Alarm signals The equipment offers various possibilities for signalling alarm conditions, however, not for danger situations. The signals may be optical (on the display as text), acoustic (piezo buzzer) or electronic (pin/status output of an analog interface). All alarms will cause the device to switch off the DC terminal.
PSB 9000 2.5 kW Series 1.8.3 Specific technical data 2.5 kW Model PSB 9060-120 PSB 9080-120 PSB 9200-70 AC supply Leak current Two phase (L-L): 208 V, ±10%, 45...66 Hz Single phase (L-N): 220 / 230 / 240 V, ±10%, 45...66 Hz < 3.5 mA Power factor ≈ 0.99 Efficiency of energy recovery ≤ 92.5% ≤ 92.5% ≤ 93.5% Max. voltage UMax 60 V 80 V 200 V Max. current IMax 120 A 120 A 70 A Max. power PMax 2500 W 2500 W 2500 W Overvoltage protection range 0...66 V 0...88 V 0...
PSB 9000 2.5 kW Series Model 2.5 kW PSB 9060-120 PSB 9080-120 PSB 9200-70 0…2550 W Power regulation Adjustment range 0…2550 W 0…2550 W Accuracy (1 (at 23 ± 5 °C / 73±9 °F) < 1% PMax < 1% PMax < 1% PMax Line regulation at ±10% ΔUAC < 0.05% PMax < 0.05% PMax < 0.05% PMax Load reg. at 10-90% ΔUDC * ΔIDC < 0.75% PMax < 0.75% PMax < 0.75% PMax Display: Resolution See section „1.9.6.4. Resolution of the displayed values“ Display: Accuracy (2 ≤ 0.3% PMax ≤ 0.3% PMax ≤ 0.
PSB 9000 2.5 kW Series 2.5 kW Model PSB 9360-40 PSB 9500-30 PSB 9750-20 AC supply Leak current Two phase (L-L): 208 V, ±10%, 45...66 Hz Single phase (L-N): 220 / 230 / 240 V, ±10%, 45...66 Hz < 3.5 mA Power factor ≈ 0.99 Efficiency of energy recovery ≤ 93.5% ≤ 94.5% ≤ 94.5% Max. voltage UMax 360 V 500 V 750 V Max. current IMax 40 A 30 A 20 A Max. power PMax 2500 W 2500 W 2500 W Overvoltage protection range 0...396 V 0...550 V 0...825 V Overcurrent protection range 0...44 A 0..
PSB 9000 2.5 kW Series Model 2.5 kW PSB 9360-40 PSB 9500-30 PSB 9750-20 0…2550 W Power regulation Adjustment range 0…2550 W 0…2550 W Accuracy (1 (at 23 ± 5 °C / 73±9 °F) < 1% PMax < 1% PMax < 1% PMax Line regulation at ±10% ΔUAC < 0.05% PMax < 0.05% PMax < 0.05% PMax Load reg. at 10-90% ΔUDC * ΔIDC < 0.75% PMax < 0.75% PMax < 0.75% PMax Display: Resolution See section „1.9.6.4. Resolution of the displayed values“ Display: Accuracy (2 ≤ 0.3% PMax ≤ 0.3% PMax ≤ 0.
PSB 9000 2.5 kW Series Views A - Power switch B - Control panel C - Control interfaces (digital, analog) D - Share Bus and remote sensing connection E - DC terminal (view shows type 1) F - AC input connection (EU model shown) G - Master-Slave ports H - Plug fixture & strain relief 1.8.4 Figure 1 - Front view EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Germany Figure 2 - Rear view (standard version) Fon: +49 2162 / 3785-0 Fax: +49 2162 / 16230 www.elektroautomatik.
Figure 3 - Side view (left) Figure 4 - Side view (right) PSB 9000 2.5 kW Series EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Germany Fon: +49 2162 / 3785-0 Fax: +49 2162 / 16230 www.elektroautomatik.de ea1974@elektroautomatik.
PSB 9000 2.5 kW Series Figure 5 - Top view EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Germany Fon: +49 2162 / 3785-0 Fax: +49 2162 / 16230 www.elektroautomatik.de ea1974@elektroautomatik.
PSB 9000 2.5 kW Series 1.8.5 Control elements Figure 6- Control Panel Overview of the elements on the control panel For a detailed description see section „1.9.6. The control panel (HMI)“. Touchscreen display (1) Used for selection of set values, menus and settings, as well as display of actual values and status. The touchscreen can be operated with the fingers or with a stylus.
PSB 9000 2.5 kW Series 1.9 Construction and function 1.9.1 General description The power supplies of the PSB 9000 series are so-called bidirectional devices, incorporating the function of a laboratory power supply (source) and an electronic load (sink) into one unit. They allow for easy setup of applications according to the source-sink principle with a minimum of required hardware and cabling.
PSB 9000 2.5 kW Series 1.9.3 Scope of delivery 1 x Bidirectional power supply device 1 x Share Bus plug 1 x Remote sensing plug 1 x 1.8 m (5.9 ft) USB cable 1 x Set of DC terminal covers 1 x Share/Sense terminal cover (only with models from 500 V) 1 x USB stick with documentation and software 1 x AC connector plug (clamp type) 1 x Set for strain relief & plug fixture (pre-mounted) 1.9.4 Accessories For these devices the following accessories are available: Interface modules IF-AB 1.9.
PSB 9000 2.5 kW Series 1.9.6 The control panel (HMI) The HMI (Human Machine Interface) consists of a display with touch screen, two rotary knobs, a pushbutton and an USB port. 1.9.6.1 Touchscreen display The graphic touchscreen display is divided into a number of areas. The complete display is touch sensitive and can be operated by finger or stylus to control the equipment.
PSB 9000 2.5 kW Series • Status display (upper right) This area displays various status texts and symbols: Display Description The HMI is locked The HMI is unlocked Remote: The device is under remote control from.... Analog ....the built-in analog interface USB & others ....the built-in USB port or a plug in interface module Local The device has been locked by the user explicitly against remote control Alarm: Alarm condition which has not been acknowledged or still exists.
PSB 9000 2.5 kW Series 1.9.6.4 Resolution of the displayed values In the display, set values can be adjusted in fixed increments. The number of decimal places depends on the device model. The values have 4 or 5 digits. Actual and set values always have the same number of digits. Adjustment resolution and number of digits of set values in the display: Resistance, R-max Nominal 25 Ω 150 Ω - 520 Ω ≥ 1000 Ω Digits Power, OPP, OPD, P-max Min. Nominal* increment 2500 W 4 1W MS 4 0.
PSB 9000 2.5 kW Series File name Description battery_test_log_.csv Section File with log data recorded from the battery test function. For 3.11.16.7 a battery test log, data different and/or additional to log data of normal USB logging is recorded. mpp_result_.csv Result data from MPP tracking mode 4 in form of a table with 100 3.11.17.6 data groups (Umpp, Impp, Pmpp) psb_pv.csv PF function table data, as calculated by the device. Can be 3.11.13 loaded again. psb_fc.
PSB 9000 2.5 kW Series 1.9.9 Analog interface This 15 pole Sub-D socket on the back side of the device is provided for remote control of the device via analog or digital signals. If remote control is in operation this analog interface can only be used alternately to the digital interface. However, monitoring is always available.
PSB 9000 2.5 kW Series 1.9.13 GPIB port (optional) The optional GPIB connector, which is available with option 3W, will replace the module slot of standard version devices. The device then offers a three-way interface with GPIB, USB and analog. The connection to a PC or other GPIB port is done with standard GPIB cables from stock, which can have straight or 90° connectors. When using cable with 90° connectors, the USB port will be inaccessible. EA Elektro-Automatik GmbH Helmholtzstr.
PSB 9000 2.5 kW Series 2. Installation & commissioning 2.1 Transport and storage 2.1.1 Transport • The handles on the front side of the device are not for carrying! • Because of its weight, transport by hand should be avoided where possible. If unavoidable then only the housing should be held and not on the exterior parts (handles, DC terminal, rotary knobs).
PSB 9000 2.5 kW Series 2.3.2 Preparation Mains connection for a device with a 2.5 kW power rating is done via the included 5 pole socket on the back of the device. Wiring of the included plug requires a 3 wire lead of suitable cross section and length. For recommendations about cable cross section see „2.3.4. Connection to AC supply“. The device mustn’t be operated on a standard wall socket. It requires a rigid connection to a properly fused supply point. See section 2.3.4.
PSB 9000 2.5 kW Series 2.3.4 Connection to AC supply • Connection to an AC supply must only be carried out by qualified personnel and the device must always be run directly on a power grid (transformer are permitted) and not on generators or UPS equipment! • Cable cross section must be suitable for the maximum input current of the device! See tables below.
PSB 9000 2.5 kW Series 2.3.4.3 Strain relief and plug fixture There is a standard fixture mounted to the AC input connection block on the rear. It’s used to prevent the AC plug from loosening and disconnecting due to vibrations or similar. The fixture is also used as strain relief. Using the 4x M3 acorn nuts, it’s recommend to mount the fixture to the AC filter block every time the AC plug has been plugged again.
PSB 9000 2.5 kW Series 2.3.4.5 Protecting the electrical installation when using energy recovering devices A PSB 9000 device recovers energy and feeds it back into the local power grid. The generated current adds to the grid current (see schematic below) and this can lead to an overload of the existing installation. Considering any two outlets, no matter of what kind they are, there is usually no extra fusing installed. In case of a defect in the AC part (i.e.
PSB 9000 2.5 kW Series 2.3.5 Connection to DC loads or DC sources • In the case of a device with a high nominal current and hence a thick and heavy DC connection cable it’s necessary to take account of the weight of the cable and the strain imposed on the DC connection. Especially when mounted in a 19” cabinet or similar, where the cable could hang on the DC terminal, a strain reliever should be used.
PSB 9000 2.5 kW Series 2.3.5.2 Cable lead and plastic cover A plastic cover for contact protection is included for the DC terminal. It should always be installed. The cover for type 2 (see picture above) is fixed to the connector itself, for type 1 to the back of the device. Furthermore the cover for type 1 has break outs so that the supply cable can be laid in various directions.
PSB 9000 2.5 kW Series Figure 8 - Example for remote sensing wiring with load in source mode (sink mode will be wired identically) 2.3.9 Installation of an interface module The optionally obtainable interface modules can be retrofitted by the user and are exchangeable with each other. The settings for the currently installed module vary and need to be checked and, if necessary, corrected on initial installation and after module exchange.
PSB 9000 2.5 kW Series 2.3.10 Connecting the “Share” bus The “Share” bus connector on the back side is usually connected to the Share bus connectors of further units of series PSB 9000, in order to balance the current between multiple units in parallel operation, especially when using the integrated function generator of the master unit. For further information about parallel operation refer to section „3.12.1. Parallel operation in master-slave (MS)“.
PSB 9000 2.5 kW Series 3. Operation and application 3.1 Terms The device is a combination of a power supply and an electronic load.
PSB 9000 2.5 kW Series The same occurs with a positive load step, i.e. low load to high load. There the output collapses for a moment. The amplitude of the overshoot or collapse depends on the device model, the currently adjusted output voltage and the capacity on the DC terminal and can thus not be stated with a specific value. Depictions: Example for neg. load step: the DC output voltage will rise above the adjusted value for a short time. t = transient time to settle the output voltage. 3.3.
PSB 9000 2.5 kW Series 3.3.4 Internal resistance regulation (source mode) Internal resistance control (short: CR) of power supplies is the simulation of a virtual internal resistor which is in series to the load. According to Ohm’s law, this resistance causes a voltage drop, which will result in a difference between the adjusted output voltage and the actual output voltage.
PSB 9000 2.5 kW Series 3.3.6 Sink-source mode switching The switchover between sink and source mode happens automatically and only depends on the device’s voltage setting and actual value on the DC terminal or the remote sense connector, if in use. It means, that when connecting an external voltage source to the DC terminal, only the voltage set value determines the operation mode. When connecting a load which can’t generate a voltage, only source mode can be run.
PSB 9000 2.5 kW Series 3.4 Alarm conditions This section only gives an overview about device alarms. What to do in case your device indicates an alarm condition is described in section „3.7. Alarms and monitoring“. As a basic principle, all alarm conditions are signaled optically (text + message in the display) and acoustically (if activated), as well as status via digital interface. In addition, the alarms are reported as signals on the analog interface.
PSB 9000 2.5 kW Series 3.4.6 Safety OVP This extra feature is only built into the 60 V model of this series. Similar to the regular overvoltage protection (OVP, see 3.4.3), the Safety OVP is supposed to protect the application or people according to SELV. The alarm shall prevent the device from providing an output voltage higher than 60 V. However, the alarm could also be triggered by an external source providing an excess voltage to the DC input of the device.
PSB 9000 2.5 kW Series 3.5 Manual operation 3.5.1 Switching on the device The device should, as far as possible, always be switched on using the rotary switch on the front of the device. Alternatively this can take place using an external cutout (contactor, circuit breaker) of suitable current capacity. After switching on, the display will first show some device related information (model, firmware versions etc.) and then a language selection screen for 3 seconds.
PSB 9000 2.5 kW Series 3.5.3.1 Menu “General Settings” Setting Allow remote control Description Selection “NO” means that the device can’t be remotely controlled over either the digital or analog interfaces. If remote control isn’t allowed, the status will be shown as “local” in the status area on the main display. See also section 1.9.6.1 Analog interface range Selects the voltage range for the analog set values, actual values and reference voltage output. • 0...5 V = Range is 0...
PSB 9000 2.5 kW Series Setting DC terminal after remote Description Determines the condition of the DC terminal after leaving remote control either manually or by command: • OFF = DC terminal will be always off when switching from remote to manual • AUTO = DC terminal will keep the last condition Enable R mode Activates (“Yes”) or deactivates (“No”) the internal resistance control. If activated, the resistance set value can be adjusted on the main screen as additional value. For details refer to „3.3.4.
PSB 9000 2.5 kW Series Profibus DP IF Level 1 Node Address Description Selection of the Profibus or node address of the device within range 1...125 via direct input Function Tag String input box for a user-definable text which describes the Profibus slave function tag. Max. length: 32 characters Location Tag String input box for a user-definable text which describes the Profibus slave location tag. Max.
PSB 9000 2.5 kW Series Level 2 Description Selection of the CANopen node address in the range 1...127 Baud Rate AUTO Automatic detection of the bus baud rate.(speed) LSS Automatically sets baud rate and node address Manual Manual selection of the baud rate that is used by the CANopen interface.
PSB 9000 2.5 kW Series RS232 IF Level 1 - Element Com Timeout Description The baud rate is selectable, other serial settings can’t be changed and are defined like this: 8 data bits, 1 stop bit, parity = none Baud rates: 2400, 4800, 9600, 19200, 38400, 57600, 115200 Description Timeout USB/RS232 (in milliseconds) Default value: 5, Range: 5...65535 Defines the max. time between two subsequent bytes or blocks of a transferred message.
PSB 9000 2.5 kW Series 3.5.4 Adjustment limits Adjustment limits are only effective on the related set values, no matter if using manual adjustment or remote control setting! Defaults are that all set values (U, I, P, R) are adjustable from 0 to 102%. The full range may be obstructive in some cases, especially for protection of applications against overvoltage. Therefore upper and lower limits for current (I) and voltage (U) can be set separately, which then limit the range of the adjustable set values.
PSB 9000 2.5 kW Series 3.5.6 Manual adjustment of set values The set values for voltage, current and power are the fundamental operating possibilities of a power supply and hence the two rotary knobs on the front of the device are always assigned to two of the values in manual operation. For each mode, sink and source, the device has separately adjustable set values for current, power and resistance which are labelled accordingly in the display.
PSB 9000 2.5 kW Series 3.5.7 Switching the DC terminal on or off The DC terminal of the device can be manually or remotely switched on and off. This can be restricted in manual operation by the control panel being locked. After switching it on, it either works as input (sink mode) or output (source mode). More information can be found in „3.3.6. Sink-source mode switching“.
PSB 9000 2.5 kW Series 3.5.8.
PSB 9000 2.5 kW Series 3.6 Remote control 3.6.1 General Remote control is possible via the built-in analog or USB port or via one of the optional interface modules (only with standard models) or via the GPIB port (only with option 3W installed). Important here is that only the analog or one digital interface can be in control. One of the digital ones is the master-slave bus.
PSB 9000 2.5 kW Series 3.6.3.2 General information about the interface modules With the standard models of series PSB 9000, one of the plug-in and retrofittable modules listed in 3.6.3.1 can be installed. It can take over remote control of the device alternatively to the built-in USB type B on the back side or analog interface. For installation see section „2.3.9. Installation of an interface module“ and separate documentation.
PSB 9000 2.5 kW Series 3.6.4.2 Resolution The analog interface is internally sampled and processed by a digital microcontroller. This causes a limited resolution of analog steps. The resolution is the same for set values (VSEL etc.) and actual values (VMON/CMON) and is 26214 when working with the 10 V range. In the 5 V range this resolution halves. Due to tolerances, the truly achievable resolution can be slightly lower. 3.6.4.
PSB 9000 2.5 kW Series * AI = Analog Input, AO = Analog Output, DI = Digital Input, DO = Digital Output, POT = Potential ** Internal Vcc approx. 10 V *** Only one of both signals possible, see section 3.5.3.1 **** Only during remote control ***** The error of a set value input adds to the general error of the related value on the DC terminal of the device 3.6.4.5 Overview of the Sub-D socket 3.6.4.
PSB 9000 2.5 kW Series Following situations can occur: • Remote control has been activated During remote control via analog interface, only pin “REM-SB” determines the states of the DC terminal, according to the levels definitions in 3.6.4.4. The logical function and the default levels can be inverted by a parameter in the setup menu of the device. See 3.5.3.1. If the pin is unconnected or the connected contact is open, the pin will be HIGH.
PSB 9000 2.5 kW Series c) Reading actual values The AI provides the DC terminal values as current and voltage monitor. These can be read using a standard multimeter or similar. d) Switching between source and sink mode You can also switch between both modes when remotely controlling the device with the AI. This is done using the voltage set value (VSEL), which then must not be tied to a fixed potential, like shown in example b).
PSB 9000 2.5 kW Series 3.7 Alarms and monitoring 3.7.1 Definition of terms There is a clear distinction between device alarms (see „3.4. Alarm conditions“) such as overvoltage protection or overheating protection, and user defined events such as OVD (overvoltage detection).
PSB 9000 2.5 kW Series These device alarms can’t be configured and are based on hardware: Short Long Description Indication PF Power Fail AC supply over- or undervoltage. Triggers an alarm if the AC supply is out of specification or when the device is cut from supply, for example Display, analog & when switching it off with the power switch. The DC terminal will be digital interface switched off. OT OverTemperature Triggers an alarm if the internal temperature reaches a certain limit.
PSB 9000 2.5 kW Series These events shouldn’t be confused with alarms such as OT and OVP which are for device protection. User defined events can, however, if set to action ALARM, switch off the DC terminal and thus protect the load, like a sensitive electronic application. ►►How to configure user defined events 1. While the DC terminal is switched off tap the touch area on the main screen. 2. On the right side tap the arrows 3. to select “7.1 Event U Src” or “7.2 Event I Src” or “7.
PSB 9000 2.5 kW Series 3.9 Limits lock In order to avoid the alteration of the adjustment limits (also see „3.5.4. Adjustment limits“) by an unprivileged user, the screen with the adjustment limit settings (“Limits”) can be locked by a PIN code. The menu pages for the limits in SETTINGS and the profiles in MENU will then become inaccessible until the lock is removed by entering the correct PIN or in case it has been forgotten, by resetting the device as last resort. ►►How to lock the “Limits” 1.
PSB 9000 2.5 kW Series 3.11 The function generator 3.11.1 Introduction The built-in function generator (short: FG) is able to create various signal forms and apply these to the set value of either voltage or current. The standard functions are based on an arbitrary generator and directly accessible and configurable using manual control. In remote control, the fully customizable arbitrary generator replicates these functions with sequence points containing 8 parameters each.
PSB 9000 2.5 kW Series 3.11.2.3 Resolution Amplitudes generated by the arbitrary generator have an effective resolution of approx. 52428 steps. If the amplitude is very low and the time long, the device would generate less steps and set multiple identical values after another, generating a staircase effect. It’s furthermore not possible to generate every possible combination of time and a varying amplitude (slope). 3.11.2.
PSB 9000 2.5 kW Series 3.11.4 Manual operation 3.11.4.1 Function selection and control Via the touch screen one of the functions described in 3.11.1 can be selected, configured and controlled. This is only permissible while the DC terminal is switched off. ►►How to select a function and adjust parameters 1. While the DC terminal is switched off tap the touch area on the main screen. 2. In the menu tap on the touch area 3. and then on the desired function.
PSB 9000 2.5 kW Series 3.11.
PSB 9000 2.5 kW Series Schematic diagram: Application and result: A triangular wave signal for use on the current or voltage is generated. The positive and negative slope times can be set independently. U,I The offset shifts the signal on the Y axis. Amplitude The sum of the intervals t1 and t2 gives the cycle time and its reciprocal is the frequency. Offset Example: a frequency of 10 Hz is required and would lead to periodic duration of 100 ms. This 100 ms can be freely allocated to t1 and t2, e. g.
PSB 9000 2.5 kW Series 3.11.
PSB 9000 2.5 kW Series Schematic diagram: Application and result: If the function is set up to run in source mode, the builtin load function acts as a sink and ensures the quick output voltage drop as required for some parts of the curve, allowing the output voltage progress to follow the DIN curve. U U start The curve conforms to test impulse 4 of the DIN. With suitable settings, other test impulses can be simulated.
PSB 9000 2.5 kW Series After the settings for the selected sequence point are accepted with SAVE, further points can be configured. In a second settings screen, which can be reached by tapping NEXT in the sequence point selection screen, following global settings for all 99 points are adjustable: Value Range Description Start seq. 1...End seq. First sequence point in the block End seq. Start seq...99 Last sequence point in the block Seq. Cycles ∞ or 1...
PSB 9000 2.5 kW Series Schematic diagram: Applications and results: U,I Example 5 Focussing 1 cycle of 1 sequence point: End (DC) Start (DC) Similar to example 1 but with a start and end frequency of 0 Hz. Without a frequency no sine wave part (AC) will be created and only the DC settings will be effective. A ramp with a horizontal progression is generated. t Seq.
PSB 9000 2.5 kW Series Schematic diagram: Applications and results: Example 9 U,I Focussing 1 cycle of 4 sequence points: Point 1: 1/4th sine wave (angle = 270°) Point 2: Three sine waves (ratio of frequency to sequence time: 1:3) Point 3: Horizontal ramp (f = 0) Point 4: Falling ramp (f = 0) Point 1 Point 2 Pt. 3 Point 4 t 3.11.10.
PSB 9000 2.5 kW Series ►►How to load a sequence table from an USB stick: 1. Do not plug the USB drive yet or remove it. 2. Access the function selection menu of the function generator with MENU -> Function Generator -> Arbitrary -> U/I, to see the main screen of sequence point selector, as depicted to the right. 3. Tap touch area , then and follow the instructions on screen.
PSB 9000 2.5 kW Series Schematic diagram: Application and result: This function generates a rising or falling ramp between start and end values over the time t2. Time t1 creates a delay before the ramp starts. U,I The function runs once and stops at the end value. To have a repeating ramp, function Trapezoid would have to be used instead (see 3.11.8). U(I)start U(I)End Important to consider are the static values of U and I which define the start levels at the beginning of the ramp.
PSB 9000 2.5 kW Series ►►How to load an IU table from an USB drive: 1. Do not plug the USB drive yet or pull it out if already plugged. 2. Open the function selection menu of the function manager with MENU -> Function Generator -> XY Table 3. In the next screen select the desired function with either „IU Table (EL)“ for running the function in sink mode 4. or “IU Table (PS)” to run the function in source mode. Configure the global parameters for U, I and P, if necessary. 5. Tap touch area 6.
PSB 9000 2.5 kW Series Schematic diagram: Application and result: Adjust all four parameters on screen to the desired values. I While the simulation is running, the user can see from the actual values (voltage, current, power) of the DC output, where the operating point of the power supply or of the simulated solar panel is. The adjustable value Irradiance (0%...
PSB 9000 2.5 kW Series 3.11.14 FC table function (fuel cell) 3.11.14.1 Preface The FC table function is used to simulate the characteristics of voltage and current of a fuel cell. This is achieved by setting up some parameters which define points on a typical fuel cell curve, which is then calculated as UI table and passed to the internal function generator. The user has to adjust value for four support points.
PSB 9000 2.5 kW Series The function can be saved to USB stick as table, as well as read via any of the digital interfaces. In remote control, the function can’t be loaded or controlled. From the screen where the XY function generator is controlled manually (start/stop), you can go back to the first screen of the FC table function and use the formerly locked touch area to save the table to USB drive. In order to do so, follow the on-screen instructions.
PSB 9000 2.5 kW Series 3.11.15.4 Simulation mode Apart from the panel technology there is also a simulation mode to select. Four options: Mode U/I Controllable simulation. Voltage (UMPP, in V) and current (IMPP, in A) in the maximum power point (MPP) are variable during runtime. The purpose of this mode is to directly shift the MPP into various directions. Mode E/T Controllable simulation.
PSB 9000 2.5 kW Series 3.11.15.6 Interpolation The interpolation feature can calculate and set intermediate steps when running the PV function in day trend mode, i. e. DAY E/T or DAY U/I. The calculation is always done between to succeeding points on the day trend curve. The dwell time of every curve point is adjustable between 500 and 1,800,000 milliseconds (see above, format of the day trend data file).
PSB 9000 2.5 kW Series 3.11.15.8 Configuration step by step Starting point In MENU->Function Generator->2nd page->XY-Table you will find the PV functions. Select PV DIN EN 50530 (PS). Step 1: Technology selection The extended PV function requires to select the panel technology of the solar panel which is going to be simulated. In case cSI or Thin Film don’t match your requirements or you are not sure about their technology parameters, select Manual.
PSB 9000 2.5 kW Series Step 4: Global limits This configuration screen allows to limit voltage and power globally for the simulation. The current, in this table based simulation, is taken from the calculated PV table which also is an IU table. The output voltage of the power supply is already defined by setting up UOC in step 2, so it’s recommended to adjust value U to same or higher, else the PV curve may not be working as expected. The power shouldn’t be limited at all.
PSB 9000 2.5 kW Series 3.11.16 Battery test function The purpose of the battery test function is to charge and discharge various battery types in industrial product tests or laboratory applications. Additionally, the so-called dynamic test mode combines a certain flow of charge and discharge phases while offering full configurability, for example which phase starts first or how much time in between both (pause) phases has to elapse or how often the charge/discharge cycle is going to be repeated.
PSB 9000 2.5 kW Series 3.11.16.1 Settings for the static discharge mode The following parameters can be configured for the static discharge battery test function: Value Range Description I 0...INom Maximum discharge current (in Ampere) P 0...PNom Maximum discharge power (in Watt) R RMin..RMax | OFF Maximum discharge resistance in Ω 3.11.16.
PSB 9000 2.5 kW Series Value Range Description Action NONE, SIGNAL, End of test Separately defines an action for the settings „Discharge time“, “Charge time”, “Discharge capacity“, “Charge capacity” and “Battery test time”.
PSB 9000 2.5 kW Series 3.11.16.8 Possible reasons for battery test stop The battery test function run can be stopped by different reasons: • • • • • • Manual stop on the HMI with button STOP After the max. test time has been reached and action “End of test” was set for it After the max.
PSB 9000 2.5 kW Series 3.11.17 MPP tracking function MPP stands for the maximum power point (see principle view to the right) on the power curve of solar panels. Solar inverters, when connected to such panels, constantly track this MPP once it has been found. The device imitates this behavior in sink mode. It can be used to test even huge solar panels without having to connect a usually big solar inverter device which also requires to have a load connected to its AC output.
PSB 9000 2.5 kW Series Following parameters can be configured for tracking mode MPP2: Value Range Description UOC 0...UNom Voltage of the solar panel when unloaded, taken from the panel specs ISC 0...INom Short-circuit current, taken from the panel specs Δt 5 ms...60000 ms Interval for measuring U and I during the process of finding the MPP ΔP 0 W...0.5 PNom Tracking/regulation tolerance below the MPP 3.11.17.
PSB 9000 2.5 kW Series ►►How to load a curve data file for MPP4 1. While the DC terminal is switched off, enter the MENU and the Function Generator and access MPP 2. 3. Tracking. In the screen switch to tab MPP4. In the lower part a button labelled Import/Export will appear. Tap it. In the next screen tap on LOAD MPP4 voltage values from USB, have your USB stick ready and follow the instructions. 3.11.17.
PSB 9000 2.5 kW Series 3.12 Other applications 3.12.1 Parallel operation in master-slave (MS) Multiple devices of same kind and model can be connected in parallel in order to create a system with higher total current and hence higher power. For parallel operation in master-slave mode the units are usually connected with their DC terminals, their Share bus and their master-slave bus, which is a digital bus that makes the system work as one big unit regarding adjusted values, actual values and status.
PSB 9000 2.5 kW Series A max. of 16 units can be connected via Share bus. 3.12.1.4 Wiring and set-up of the digital master-slave bus The master-slave connectors are built-in and can be connected via network cables (≥CAT3, patch cable). After this, MS can be configured manually or by remote control. The following applies: • A maximum of 16 units can be connected via the bus: 1 master and up to 15 slaves. • Only devices of same kind, i.e.
PSB 9000 2.5 kW Series ►►Step 2: Configuring the master unit 1. Enter , then GENERAL SETTINGS and press 2. Specify the unit as master with touch area until reaching the master-slave settings. . A warning requester will appear which has to be acknowledged with OK, otherwise the change will be reverted. 3. Accept the settings with the touch area and return to the main page.
PSB 9000 2.5 kW Series • Loss of connection to any slave will result in shutdown of all DC terminals, as a safety measure, and the master will report this situation in the display with a pop-up “Master-slave security mode”. Then the MS system has to be re-initialised, either with or without re-establishing connection to the disconnected unit(s) before. • All units, even the slaves, can be externally shut down on the DC terminals using the pin REM-SB of the analog interface.
PSB 9000 2.5 kW Series 3.12.3 Operation as battery charger (source mode) A power supply (here: PSB 9000 in source mode) can be used as a battery charger, but with some restrictions, because it misses a battery supervision and a physical separation from the load in form of a relay or contactor, which is sometimes featured with real battery chargers as a protection.
PSB 9000 2.5 kW Series 4.3 Calibration 4.3.1 Preface The devices of series PSB 9000 don’t have a built- in feature to re-adjust the most important DC terminal related values, but they can still be readjusted using the software EA Power Control. The required calibration app is included in the free of charge base version of this software. In order to use the feature is may be necessary to install a n update of this software.
PSB 9000 2.5 kW Series 5. Contact and support 5.1 Repairs 5.2 Contact options Repairs, if not otherwise arranged between supplier and customer, will be carried out by the manufacturer. For this the device must generally be returned to the manufacturer. No RMA number is needed. It’s sufficient to package the equipment adequately and send it, together with a detailed description of the fault and, if still under guarantee, a copy of the invoice, to the following address.
EA Elektro-Automatik GmbH & Co. KG Development - Production - Sales Helmholtzstraße 31-37 41747 Viersen Germany Fon: +49 2162 / 37 85-0 Mail: ea1974@elektroautomatik.de Web: www.elektroautomatik.