User Manual

Table Of Contents
Page 10
PSI 9000 3U Series
www.elektroautomatik.de
ea1974@elektroautomatik.de
EA Elektro-Automatik GmbH
Helmholtzstr. 31-33 • 41747 Viersen
Germany
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
1.9.3 Specic technical data
(1Relatedtothenominalvalues,theaccuracydenesthemaximumdeviationbetweenanadjustedvaluesandthetrue(actual)value.
Example: a 80 V model has min. 0.1% voltage accuracy, that is 80 mV. When adjusting the voltage to 5 V, the actual value is allowed to differ max. 80 mV, which
means it might be between 4.92 V and 5.08 V.
(2 RMS value: LF 0...300 kHz, PP value: HF 0...20MHz
(3 Typical value at 100% output voltage and 100% power
(4 Set values as in the display or as data readable via digital interfaces are more accurate than the corresponding value on the DC output. Their accuracy subtracts
from the general accuracy. For actual values it is vice versa. There the display accuracy adds to the general accuracy, so the error (i.e. deviation) will be higher.
3.3 kW / 5 kW
Model 3U
PSI 9040-170 PSI 9080-170 PSI 9200-70 PSI 9360-40 PSI 9500-30
AC Input
Input voltage 340...460 V AC 340...460 V AC 340...460 V AC 340...460 V AC 340...460 V AC
Input connection 2ph,PE 2ph,PE 2ph,PE 2ph,PE 2ph,PE
Input frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Input fuse (internal) 2x T16 A 2x T16 A 2x T16 A 2x T16 A 2x T16 A
Leak current < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA
Power factor > 0.99 > 0.99 > 0.99 > 0.99 > 0.99
DC Output
Max. output voltage U
Max
40 V 80 V 200 V 360 V 500 V
Max. output current I
Max
170 A 170 A 70 A 40 A 30 A
Max. output power P
Max
3.3 kW 5 kW 5 kW 5 kW 5 kW
Voltage regulation
Adjustment range 0...40 V 0...80 V 0...200 V 0...360 V 0...500 V
Overvoltage protection range 0...44 V 0...88 V 0...220 V 0...396 V 0...550 V
Accuracy
(1
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
Stabilityat±10%ΔU
AC
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
Stability at 0...100% load < 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
Rise time 10...90% Max. 30 ms Max. 30 ms Max. 30 ms Max. 30 ms Max. 30 ms
Display: Resolution See section „1.10.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤0.2%U
Max
≤0.2%U
Max
≤0.2%U
Max
≤0.2%U
Max
≤0.2%U
Max
Ripple
(2
< 100 mV
PP
< 10 mV
RMS
< 100 mV
PP
< 10 mV
RMS
< 200 mV
PP
< 25 mV
RMS
< 250 mV
PP
< 50 mV
RMS
< 250 mV
PP
< 70 mV
RMS
Remote sensing compensation Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Fall time at no load after switching
DC output off
- Down from 100% to <60 V: less than 10 s
Current regulation
Adjustment range 0...170 A 0...170 A 0...70 A 0...40 A 0...30 A
Overcurrent protection range 0...187 A 0...187 A 0...77 A 0...44 A 0...33 A
Accuracy
(1
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
Stabilityat±10%ΔU
AC
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
Stabilityat0...100%ΔU
OUT
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
Ripple
(2
< 528 mA
PP
< 106 mA
RMS
< 300 mA
PP
< 40 mA
RMS
< 44 mA
PP
< 11 mA
RMS
< 32 mA
PP
< 6 mA
RMS
< 14 mA
PP
< 8 mA
RMS
Display: Resolution See section „1.10.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤0.2%I
Max
≤0.2%I
Max
≤0.2%I
Max
≤0.2%I
Max
≤0.2%I
Max
Compensation 10%->90% load < 1.5 ms < 1.5 ms < 1.5 ms < 1.5 ms < 1.5 ms
Power regulation
Adjustment range 0…3.30 kW 0…5.00 kW 0…5.00 kW 0…5.00 kW 0…5.00 kW
Overpower protection range 0…3.63 kW 0…5.50 kW 0…5.50 kW 0…5.50 kW 0…5.50 kW
Accuracy
(1
< 1% P
Max
< 1% P
Max
< 1% P
Max
< 1% P
Max
< 1% P
Max
Stabilityat±10%ΔU
AC
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
Stabilityat10-90%ΔU
OUT
*ΔI
OUT
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
Display: Resolution See section „1.10.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤0.75%P
Max
≤0.8%P
Max
≤0.8%P
Max
≤0.8%P
Max
≤0.8%P
Max
Efciency
(3
~ 93% ~ 93% ~ 95% ~ 95% ~ 95,5%