User Manual
48
© 2006, Elektro-Automatik GmbH & Co. KG
Irrtümer und Änderungen vorbehalten
EN
Instruction Manual
PSI 8000 3U Series
Date: 03-22-2011
About the device
PSI 8500-90 3U PSI 8600-70 3U PSI 81500-30 3U
Mains input
Input voltage range 340…460V 340…460V 340…460V
Input voltage range optional 588…796V+MP 588…796V+MP 588…796V+MP
Required phases L1, L2, L3, PE L1, L2, L3, PE L1, L2, L3, PE
Input frequency 50/60Hz 50/60Hz 50/60Hz
Input fuse 6x T16A 6x T16A 6x T16A
Input current max. 28A max. 28A max. 28A
Power factor > 0.99 > 0.99 > 0.99
Output - Voltage
Nominal voltage U
Nom
500V 600V 1500V
Adjustable range
0V…U
Nom
0V…U
Nom
0V…U
Nom
Stability at mains fluctuation ±10% ∆U
IN
< 0.02% < 0.02% < 0.02%
Stability at 0…100% load < 0.05% < 0.05% < 0.05%
Ramp-up time 10...90% at 100% load max. 30ms max. 30ms max. 30ms
Ripple @ BWL 20MHz
< 300mVpp
< 70mVrms
< 400mVpp
< 80mVrms
< 1000mVpp
< 350mVrms
Accuracy* ≤ 0.2% ≤ 0.2% ≤ 0.2%
Resolution of display 100mV 100mV 1V
Remote sense compensation max. 10V max. 18V max. 30V
Overvoltage protection
threshold (adjustable)
0…550V 0…660V 0…1650V
Output - Current
Nominal current I
Nom
90A 70A 30A
Adjustable range
0…I
Nom
0…I
Nom
0…I
Nom
Stability at mains fluctuation ±10% ∆U
IN
< 0.05% < 0.05% < 0.05%
Stability at 0…100% ∆U
OUT
< 0.15% < 0.15% < 0.15%
Ripple @ BWL 20MHz
< 50mApp
< 23mArms
< 30mApp
< 12mArms
< 19mApp
< 13mArms
Accuracy* ≤ 0.2% ≤ 0.2% ≤ 0.2%
Resolution of display 10mA 10mA 10mA
Transient recovery time 10….90% load < 2ms < 2ms < 2ms
Output - Power
Nominal power P
Nom
15000W 15000W 15000W
Nominal power at derating
0...P
Nom
0...P
Nom
0...P
Nom
Accuracy* ≤ 0.2% ≤ 0.2% ≤ 0.2%
Resolution of display 0.01kW 0.01kW 0.01kW
Efficiency 95.50% 95.20% 95.50%
Miscellaneous
Ambient temperature 0….50°C 0….50°C 0….50°C
Storage temperature -20….70°C -20….70°C -20….70°C
Humidity rel. < 80% < 80% < 80%
Dimensions (WxHxD) ** 19" 3U 595mm 19" 3U 595mm 19" 3U 595mm
Weight 33kg 33kg 33kg
Redundancy yes no no
Isolation output to enclosure 500V DC 1000V DC 1000V DC
Isolation input to output
Cooling
Safety
EMC standards
Overvoltage class
Protection class
Pollution degree
Operational altitude
Series operation
max. series connection voltage
Master-Slave
Parallel operation
max. parallel connection voltage
Master-Slave
Analogue programming
Input range
Accuracy
Input impedance
Article number 09230437 09230444 09230439
1
2
by fans, air inlet on the front, air exhaust on the rear
EN 60950
EN 61326, EN 55022 Class B
2
4200V DC
600V
no
1500V
yes, via Share bus
0…5V or 0…10V, selectable
<2000m
53kOhm
≤ 0.2%
* Related to the nominal value, the accuracy denes the maximum allowed deviation between set value and actual value.
Example: a 80V model has min. 0.2% voltage accuracy. This is 160mV. When setting a voltage of 5V and with an allowed maximum deviation of 160mV, the resulting
actual value could be between 4.84V and 5.16V.