2.3.11 Initial commission
Fortherststart-upafterpurchasingandinstallingthedevice,thefollowingprocedureshavetobeexecuted:
• Conrmthattheconnectioncablestobeusedareofasatisfactorycrosssection
• Check that the default settings for set values, safety and monitoring functions and communication are suitable
for your application and change them where necessary, as described in the manual
• In case of remote control via PC, read the additional documentation for interfaces and software
• In case of remote control via the analog interface, read the section in this manual concerning analog interfaces
and, where needed, other appropriate documentation especially concerning the use of such interfaces
2.3.12 Initial network setup
The device is delivered with default network parameters (see „3.3.3.7. Menu “Communication”“). The Ethernet/
LAN port is immediately ready for use after the initial commission.
For wiring, i.e. the hardware connection to a network, contact and ask your IT manager or any similar responsible
person. Network cable of common type (CAT5 or better) can be used.
In order to set up the network parameter to your needs, you have two options: the setup menu or the device’s
website.Forthecongurationinthesetupmenupleasereferto„3.3.3.7. Menu “Communication”“.
Forthecongurationviathedevice’swebsite,youneedthedevicetobeconnectedtoanetworkordirectlytoa
PC which can access the default IP 192.168.0.2.
How to do the network setup on the device website
1. In case the device display is in any kind of menu, lave menu to main display.
2. Open the device website in a browser by entering the default IP (http://192.168.0.2) or the default host name
(http://Client, only possible if there is a running DNS in the network) into the URL box.
3. Afterthewebsitehasbeencompletelyloaded,checkthestatuselditemAccess” to show the status “free”.
In case it shows different, the device is either already in remote control (rem) or blocked from remote control
(local). If it shows “local”,rstremovetheblock.Refertosection„3.4.2. Control locations“ to do that.
4. If it says “rem” in the “Access” item, skip to step 5. Else enter command syst:lock on (attention! space
before on) into the SCPI command box and send with return key. Check if item “Access”instatuseld
changes to “rem-eth” (means: remote Ethernet).
5. Switch to page CONFIGURATION (upper left corner) and set up the network parameters as well as the port
here resp. activate DHCP and submit the change with SUBMIT button.
6. Wait a few seconds before testing the new IP by entering it in the browser’s URL box. Opening the website
again by using the host name is only possible after the device has restarted, because only then the new IP
is reported to the DNS.
2.3.13 Commission after a rmware update or a long period of non-use
Incaseofarmwareupdate,returnoftheequipmentfollowingrepairoralocationorcongurationchange,similar
measures should be taken to those of initial start up. Refer to „2.3.11. Initial commission“.
Only after successful checking of the device as listed may it be operated as usual.