User Manual

Page 12
PS 9000 3U Series
www.elektroautomatik.de
ea1974@elektroautomatik.de
EA Elektro-Automatik GmbH
Helmholtzstr. 31-33 • 41747 Viersen
Germany
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
5 kW / 6.6 kW / 10 kW
Model 3U
PS 9750-20 PS 9040-340 PS 9040-510 PS 9080-340 PS 9200-140
AC Input
Input voltage 340...460 V AC 340...460 V AC 340...460 V AC 340...460 V AC 340...460 V AC
Input connection 2ph,PE 3ph,PE 3ph,PE 3ph,PE 3ph,PE
Input frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Input fuse (internal) 2x T16 A 4x T16 A 4x T16 A 4x T16 A 4x T16 A
Leak current < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA
Power factor > 0.99 > 0.99 > 0.99 > 0.99 > 0.99
DC Output
Max. output voltage U
Max
750 V 40 V 40 V 80 V 200 V
Max. output current I
Max
20 A 340 A 510 A 340 A 140 A
Max. output power P
Max
5 kW 6.6 kW 10 kW 10 kW 10 kW
Voltage regulation
Adjustment range 0...750 V 0...40 V 0...40 V 0...80 V 0...200 V
Overvoltage protection range 0...825 V 0...44 V 0...44 V 0...88 V 0...220 V
Accuracy
(1
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
Stabilityat±10%ΔU
AC
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
Stability at 0...100% load < 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
Rise time 10...90% Max. 30 ms Max. 30 ms Max. 30 ms Max. 30 ms Max. 30 ms
Display: Resolution See section „1.10.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤0.2%U
Max
≤0.2%U
Max
≤0.2%U
Max
≤0.2%U
Max
≤0.2%U
Max
Ripple
(2
< 600 mV
PP
< 120 mV
RMS
< 150 mV
PP
< 10 mV
RMS
< 150 mV
PP
< 10 mV
RMS
< 150 mV
PP
< 10 mV
RMS
< 200 mV
PP
< 25 mV
RMS
Remote sensing compensation Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Fall time at no load after switching
DC output off
Down from
100% to <60 V:
less than 10 s
- -
Down from
100% to <60 V:
less than 10 s
Down from
100% to <60 V:
less than 10 s
Current regulation
Adjustment range 0...20 A 0...340 A 0...510 A 0...340 A 0...140 A
Overcurrent protection range 0...22 A 0...374 A 0...561 A 0...374 A 0...154 A
Accuracy
(1
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
Stabilityat±10%ΔU
AC
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
Stabilityat0...100%ΔU
OUT
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
Ripple
(2
< 18 mA
PP
< 4 mA
RMS
< 600 mA
PP
< 80 mA
RMS
< 900 mA
PP
< 120 mA
RMS
< 600 mA
PP
< 80 mA
RMS
< 89 mA
PP
< 22 mA
RMS
Display: Resolution See section „1.10.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤0.2%I
Max
≤0.2%I
Max
≤0.2%I
Max
≤0.2%I
Max
≤0.2%I
Max
Compensation 10%->90% load < 1.5 ms < 1.5 ms < 1.5 ms < 1.5 ms < 1.5 ms
Power regulation
Adjustment range 0…5.00 kW 0…6.60 kW 0…10.00 kW 0…10.00 kW 0…10.00 kW
Overpower protection range 0…5.50 kW 0…7.26 kW 0…11.00 kW 0…11.00 kW 0…11.00 kW
Accuracy
(1
< 1% P
Max
< 1% P
Max
< 1% P
Max
< 1% P
Max
< 1% P
Max
Stabilityat±10%ΔU
AC
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
Stabilityat10-90%ΔU
OUT
*ΔI
OUT
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
Display: Resolution See section „1.10.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤0.8%P
Max
≤0.7%P
Max
≤0.7%P
Max
≤0.8%P
Max
≤0.85%P
Max
Efciency
(3
~ 94% ~ 93% ~ 93% ~ 93% ~ 95%
(1Relatedtothenominalvalues,theaccuracydenesthemaximumdeviationbetweenanadjustedvaluesandthetrue(actual)value.
Example: a 80 V model has min. 0.1% voltage accuracy, that is 80 mV. When adjusting the voltage to 5 V, the actual value is allowed to differ max. 80 mV, which
means it might be between 4.92 V and 5.08 V.
(2 RMS value: LF 0...300 kHz, PP value: HF 0...20MHz
(3 Typical value at 100% output voltage and 100% power
(4 The display accuracy adds to the general accuracy, so the error (i.e. deviation) will be higher.