1.9.3 Specic technical data
(1Relatedtothenominalvalues,theaccuracydenesthemaximumdeviationbetweenanadjustedvaluesandthetrue(actual)value.
Example: a 80 V model has min. 0.1% voltage accuracy, that is 80 mV. When adjusting the voltage to 5 V, the actual value is allowed to differ max. 80 mV, which
means it might be between 4.92 V and 5.08 V.
(2 RMS value: LF 0...300 kHz, PP value: HF 0...20MHz
(3 Typical value at 100% output voltage and 100% power
(4 The display accuracy adds to the general accuracy, so the error (i.e. deviation) will be higher.
3.3 kW / 5 kW
Model 3U
PS 9040-170 PS 9080-170 PS 9200-70 PS 9360-40 PS 9500-30
AC Input
Input voltage 340...460 V AC 340...460 V AC 340...460 V AC 340...460 V AC 340...460 V AC
Input connection 2ph,PE 2ph,PE 2ph,PE 2ph,PE 2ph,PE
Input frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Input fuse (internal) 2x T16 A 2x T16 A 2x T16 A 2x T16 A 2x T16 A
Leak current < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA
Power factor > 0.99 > 0.99 > 0.99 > 0.99 > 0.99
DC Output
Max. output voltage U
Max
40 V 80 V 200 V 360 V 500 V
Max. output current I
Max
170 A 170 A 70 A 40 A 30 A
Max. output power P
Max
3.3 kW 5 kW 5 kW 5 kW 5 kW
Voltage regulation
Adjustment range 0...40 V 0...80 V 0...200 V 0...360 V 0...500 V
Overvoltage protection range 0...44 V 0...88 V 0...220 V 0...396 V 0...550 V
Accuracy
(1
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
Stabilityat±10%ΔU
AC
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
Stability at 0...100% load < 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
Rise time 10...90% Max. 30 ms Max. 30 ms Max. 30 ms Max. 30 ms Max. 30 ms
Display: Resolution See section „1.10.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤0.2%U
Max
≤0.2%U
Max
≤0.2%U
Max
≤0.2%U
Max
≤0.2%U
Max
Ripple
(2
< 100 mV
PP
< 10 mV
RMS
< 100 mV
PP
< 10 mV
RMS
< 200 mV
PP
< 25 mV
RMS
< 250 mV
PP
< 50 mV
RMS
< 250 mV
PP
< 70 mV
RMS
Remote sensing compensation Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Fall time at no load after switching
DC output off
- Down from 100% to <60 V: less than 10 s
Current regulation
Adjustment range 0...170 A 0...170 A 0...70 A 0...40 A 0...30 A
Overcurrent protection range 0...187 A 0...187 A 0...77 A 0...44 A 0...33 A
Accuracy
(1
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
Stabilityat±10%ΔU
AC
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
Stabilityat0...100%ΔU
OUT
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
Ripple
(2
< 528 mA
PP
< 106 mA
RMS
< 300 mA
PP
< 40 mA
RMS
< 44 mA
PP
< 11 mA
RMS
< 32 mA
PP
< 6 mA
RMS
< 14 mA
PP
< 8 mA
RMS
Display: Resolution See section „1.10.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤0.2%I
Max
≤0.2%I
Max
≤0.2%I
Max
≤0.2%I
Max
≤0.2%I
Max
Compensation 10%->90% load < 1.5 ms < 1.5 ms < 1.5 ms < 1.5 ms < 1.5 ms
Power regulation
Adjustment range 0…3.30 kW 0…5.00 kW 0…5.00 kW 0…5.00 kW 0…5.00 kW
Overpower protection range 0…3.63 kW 0…5.50 kW 0…5.50 kW 0…5.50 kW 0…5.50 kW
Accuracy
(1
< 1% P
Max
< 1% P
Max
< 1% P
Max
< 1% P
Max
< 1% P
Max
Stabilityat±10%ΔU
AC
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
Stabilityat10-90%ΔU
OUT
*ΔI
OUT
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
Display: Resolution See section „1.10.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤0.75%P
Max
≤0.8%P
Max
≤0.8%P
Max
≤0.8%P
Max
≤0.8%P
Max
Efciency
(3
~ 93% ~ 93% ~ 95% ~ 95% ~ 95,5%