User's Manual

September 06, 2022
CLS-4-420-TH
8
ROTARY ENCODERS
The rotary encoders are used to set the desired reporng Interval. The rotary encoders set the broadcast
interval of the CLS-4-420-TH in 20 second increments, from 01 (20 seconds) to 09, and in 200s increments,
from 11 (200 seconds) to 91 (16200 seconds) Seng 92 to 99 is the same as 91. Seng 00 or 10 disables
broadcasts.
The broadcast interval may be set at any me. NB: Any changes to the broadcast interval aer the inial
pairing will be reected only aer the next report.
ROTARY SWITCH CODING:
Rotary Dial Setting
Reporting Interval (s)
00
0 (disabled!)
01
20
02
40
||
||
09
180
10
0 (disabled!)
11
200
12
400
||
||
21
2200
||
||
91
16200 (4.5 hrs max)
92
16200