Assembly Instructions

FEBRUARY 11, 2022
CLS-4-420-th
28
15
The Gateway Visualizer will show 20 mA
current reading on all the four (4) channels.
Set the DROK Signal Generator to dierent
current reading and check the gateway
visualizer for results.
16
If the any of four channel is not showing
current value according to DROK signal
generator display, change the resistance on
potenometer unl it is similar to DROK
signal generator display.
FINAL TEST PASS CRITERIA
Measurement
PASS Criteria
Notes
RSSI
-20 dBm to -35 dBm
Allow for up to ve (5) reports
Temperature NTC
Temperature CHIP ± 0.5◦C
Measurement should mirror the
Temperature CHIP report
Temperature CHIP
Ambient Temperature
Measurement is factory calibrated, so
reading should fall in line with ambient
condions
Humidity
Ambient Humidity
Measurement is factory calibrated, so
reading should fall in line with ambient
condions
Current 1,2,3,4
All four channels should show
current reading in between 4-
20mA
If any of the channel is not showing
current according to DROK signal
generator display adjust potenometer
resistance.
Current 1 – Potenometer R120
Current 2 – Potenometer R121
Current 3 – Potenometer R122
Current 4 – Potenometer R123