Operating Instructions
January 8, 2021
BMS-1001-TH BMS
9
CONNECTIONS
The external lead-acid baery bank is connected
to the screw terminals on the boom of the
BMS.
Each cell voltage input supports measurement
range of 0-5 VDC. Up to 10 series connected cells
may be monitored. The maximum input range of
the enre string must not exceed 36 VDC.
When less than 10 baery cells are connected,
the cells should always be wired from boom to
top, and the unconnected cells should be shorted
to the highest potenal in the baery bank.
The BMS supports connecon of a CR Magnecs
CR5210 series current transducer.
The current rmware version (3111) only
supports reporng of the CR5210-50 (± 50 A)
current transducer. Other current ranges will
operate, but the reported current from the BMS
will not be correct.
A USB type B connector and a 2.5 mm ID power
jack are on the boom of the BMS.
Both the USB connecon and the DC input will
automacally charge the internal lithium-ion
baery.
The DC input accepts a voltage range of 7 VDC to
15 VDC, with a minimum current of 2 A.
NC 10 9 8 7 6
5 4 3 2 1 0
24V INPUT GND