Operation and programming manual
23
Telephone numbers
Address 54: Primary Telephone Number
The primary telephone number is the first number that is dialed when an event occurs.
A maximum of 16 digits can be entered at this address. To add a two-second pause,
enter B (Q, 1). To switch from pulse to DTMF dialing enter E (Q, 4). These hexadecimal
digits, B and E, are included in the 16 digit total. Press ENTER after the last digit of the
telephone number has been programmed.
Address 55: Backup Telephone Number
The backup telephone number is dialed if the panel fails to communicate with the
primary number after five attempts. The backup telephone number is programmed in
the same way as the primary telephone number (address 54).
Address 56: RP Callback Telephone Number
Remote programming communication can be established using two methods,
passcode and callback (see address 02, second digit). If RP callback is selected the
panel receives a call from the remote programmer, hangs up and calls back using the
telephone number programmed at this address. The RP callback telephone number is
programmed in the same way as the primary telephone number (address 54).
Note: To disable a telephone number, enter the appropriate address and press
ENTER. It is not possible to program a backup number unless a primary number
has been programmed.
Address 57: RP Access Code
This 4-digit code grants access to the remote programmer. Note: Do not enter Hex digits.
Address 58: Account Number
When an event code is sent, the central station receives an account number to identify
the customer. Enter a 4-digit account number at this address.
Address 59: Installer Code
The installer code is a 4-digit code which grants access to programming mode. The
default for this code (1234) should be changed immediately after installing the system.
Note: Do not enter Hex digits.
4.4: Periodic Test Timer Reset
The periodic test event code (address 45) is sent to the central station once every 24
hours. The first transmission of this code is sent 24 hours after power is applied to the
control panel. If a different time is required, control panel can be programmed to send
the event code every 24 hours from the moment the periodic test timer is reset.
To reset the periodic test timer:
1. Press Q, 7 to enter programming mode.
2. Enter the Installer Code; the Armed LED lights up and the System LED flashes.
3. Enter 99; the periodic test timer is reset and the periodic test code is sent to the
central station.
4. Press # to exit programming mode.