Recording dimmer loads
When you Record Loads, the system records load information only for the
dimmers set at a level above zero. Choose the dimmers you wish to
record, set them to a level, then run Record Loads.
Record Loads records 24 dimmers per rack at a time until all dimmers at
levels above zero have been recorded. (If you have multiple racks, 24 dim-
mers in each rack are recorded simultaneously.)
Note: On single phase racks, the system records 16 dimmers per rack at
a time.
Caution: Record Loads changes levels on stage. Dimmer outputs rise and
fall for several minutes during the procedure. To cancel a Record Load
operation that has already started, press [S7], Cancel, [Enter].
Follow these steps to Record Loads for your system.
Note: If you wish, instead of setting the desired dimmers to a level in step
1, you may enter a list of dimmers to record in step 5.
Keystrokes:
Action:
1. Set desired dimmers to a
level above zero. Only
dimmers at levels above
zero are recorded.
2. Press [Setup].
Selects Setup display
3. Select [9], ETCLink Func-
tions, and press [Enter].
Selects ETCLink Functions menu
4. Select [4], Load Manage-
ment, and press [Enter].
Selects Load Management display
5. Press [S5], Record Loads.
If you wish, you may enter
a specific dimmer or dim-
mers to record.
Prompt reads:
To record loads, select dimmer(s)
and press ENTER (Enter 0 to record
loads for all dimmers)
6. Press [0] [Enter].
Advisory reads:
New loads will be recorded for all
dimmers with levels above zero.
Levels on stage will change while
the Record Load is in progress. The
system will automatically vary the
dimmer outputs during the Record
Load. The process may take several
minutes to complete.
Press [Enter] to proceed, or press
[Clear] to cancel
7. Press [Enter] to proceed
with the load record, or
press [Clear] to cancel the
operation.
New loads are recorded for all
dimmers with levels above zero