Specifications
Unison
®
Button Station
Control Series
SPECIFICATIONS
MECHANICAL Button stations shall consist of an electronic
assembly and faceplate which shall utilize a
cantilever styled switch array.
Stations shall flush mount in industry standard
1-gang back boxes (provided by others).
Surface mount back-boxes shall be available for
one-gang stations.
Station faceplates and button caps shall be
constructed of injection molded, ABS plastic.
Buttons shall contain an integral LED
response indicator.
Stations shall have no visible means of
attachment.
All station legends shall be silk-screened in a
scratch and wear resistant dark gray paint.
Button stations shall be available in white,
ivory, gray and black. Custom colors shall be
available with sample.
Button stations shall be available with 1, 2, 5, 7,
and 10 buttons. Custom button stations shall
be available.
1, 2, and 5 button stations shall be available
with a maintained or momentary keyswitch.
ELECTRICAL Button stations shall connect to Echelon*
LONWORKS* Link Power control network.
Link Power network shall utilize low voltage
Class II unshielded twisted pair, Belden type
8471 or equivalent and (1) #14 ESD drain wire
(Drain wire not required when installed in
grounded metal conduit).
Link Power network wiring shall not exceed
1500’ (500m) without the use of a repeater. The
REP, Repeater Option module shall increase
network wire length in increments of 1500’
(500m). Maximum (4) LCD’s per power supply,
total 32 stations per repeater.
The Unison station protocol is Echelon Link
Power.
Link Power network shall be topology free and
polarity independent. Wiring may be bus, loop,
home-run or any combination of these.
All station terminations shall be connectorized.
FUNCTIONAL Buttons station components shall be designed
to operate default or custom system functions.
Optional button functions shall be
programmable via Light Manager.
Button function options shall include: preset
selection, manual mode activation, record
mode activation, station lockout, raise, lower,
macro activation, zone on/off control and wall
open/close or toggle.
Button station components shall allow
programming of individual lockout levels.
DIMENSIONS
Surface Backbox Dimensions
Gang Height Width Depth
inches cm inches cm inches cm
1/2 (by ETC) 3.75 9.53 1.75 4.45 3.25 8.26
1 (RACO 690*) 3.75 9.53 2.0 5.08 2.5 6.35
*or equivalent
Flush Backbox Dimensions
Gang Height Width Depth
inches cm inches cm inches cm
1/2 (by ETC) 3.75 9.53 1.3 3.3 3.25 8.26
1 (RACO 690*) 3.75 9.53 2.0 5.08 2.5 6.35
Faceplate Dimensions
Gang Height Width
inches cm inches cm
1/2 4.5 11.43 1.75 4.45
1 4.5 11.43 2.8 7.1
Americas
■
3030 Laura Lane, P.O. Box 620979, Middleton, WI 53562-0979 USA
■
Tel: +1 608 831 4116
■
Fax: +1 608 836 1736
■
Toll free: 866 382 2724
■
Toll free fax: 800 555 8912
Europe
■
Unit 5, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK
■
Tel: +44 (0)20 8896 1000
■
Fax: +44 (0)20 8896 2000
Asia
■
Room 605-606, Tower III Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong
■
Tel: +852 2799 1220
■
Fax: +852 2799 9325
Web: www.etcconnect.com
■
Email: (US) mail@etcconnect.com
■
(UK) mail@etceurope.com
■
(Asia) mail@etcasia.com
Copyright © 2003 ETC. All Rights Reserved. All product information and specifications subject to change. 7081L1046 Rev. C Printed in USA 08/03
Barbizon Light WPI Submittal Package Page 33 of 43