Instruction manual
-26-
Operatinginstructions-systemvoltagescontinued
MAINSUPPLY and AUXSUPPLY
CONVZONE1andCONVZONE2
SOUNDER1,2and3.
MAINMENU>LIVEVALUES>HEADVALUES
LOOP NUMBER
ANALOGUEVALUE
PRE ALARM, ALARMandFAULT
LIVEDEVICECODE
CONFGDEVICECODE
HEADNUMBER
CONFIGURED
ThemainDCsupplyand AuxiliaryDC(ifused)arenominally24V+/-25%innormaluse. Thebatterywill
chargefromeitherthemainDCor AuxDCwhicheverishigher.
Bothconventionalzonesarepoweredviaaregulated20VDCsupplyandshouldbeapproximately18Vin
normalcondition.Iftheendoflineresistorisremovedthisvoltagewillriseandtheopencircuitfaultwarningwill
begiven. A shortcircuitacrossthezonewillseethevoltagefalltoalmost0Vandtheshortcircuitfaultwarning
given.Inthealarmconditiontheconventionalzonevoltagewillfalltoapproximately10Vandthealarmwarning
given. Thereisadelayofapproximately6secondsbeforeafaultoralarmconditionissignalled.
Thevoltagedisplayedisthecircuitmonitoringvoltagewhichisconnectedwithreversepolarityandshouldbe
approximately1.5Vinthenormalcondition,risingtoapproximately2.3Vforopencircuitanddroppingtonearly
0Vforashortcircuit.
.
Indicatestheloopnumberofthedevicecurrentlybeingdisplayed.Usethe+/-arrowkeystochangeloop
number.
Thisisthecurrentanaloguevaluebeingreturnedbythedevicecurrentlybeingdisplayed.ForaSounder
controlunit,asintheexampleabove,thiswouldbenormally16.Lessthan10wouldindicateafault.
Fordetectorsthisvaluewillriseasthedetectedmediumincreases(smoke,heatetc.)Forstandard Apollo
detectorsthepre-alarmvalueis45andthealarmvalueis55.
Indicateswhetherthedevicecurrentlybeingdisplayedisintheprealarm,alarmorfaultcondition.
Displaystheactual Apollotypecode,thedevicetypeandprotocolusedbythedevicecurrentlybeingdisplayed.
Displaystheconfigured Apollotypecode,thedevicetypeandprotocolusedbythedevicecurrentlybeing
displayed. ThisisthecodeenteredusingtheFireConfigsoftware.If,duringsetup,thiscodewasentered
incorrectlyandisdifferenttotheactualcodereturnedbythedevicethesystemwillgointofaultconditionand
an“incorrectdevicecodefault”messagewillbedisplayed.
Displaystheaddressofthedevicecurrentlybeingdisplayed.Usethe+/-arrowkeystochange.
Indicateswhetherthecurrentaddressisused.
10:51 05/06/08 HEADVALUES USER1
LOOP NUMBER: 1 HEADNUMBER: 20
ANALOGUEVALUE: 16 CONFIGURED: YES
PRE ALARM: NO OUTPUTBITS: 0
ALARM: NO INPUTBITS: 0
FAULT: NO PROTOCOL: XP95
LIVEDEVICECODE: 4 SNDRCTRL UNITXP95
CONFGDEVICECODE:4 SNDRCTRL UNITXP95
ED816A AddressableFireandgasdetectionInstallationmanual8-9-08Rev-a