Instruction manual
-24-
Operatinginstructions-systemsetupcontinued
MAINMENU>SYSTEMSETUP >SEARCHFORNEWDEVICES
shouldnot
MAINMENU>SYSTEMSETUP >SETTIME ANDDATE
4.MAINMENU>SYSTEMMENU
5.MAINMENU>GASDETECTION
Thesearchfornewdevicesfeatureallowsadditionaladdressabledevicestobeaddedtothesystemwithout
theuseofaPCandtheFireConfigsoftware. Thesearchwillfindallnewdevicesfittedtoaloop,however,it
beusedforgasdetectionorSoundersand/orBeaconsexceptwhenaddingtoanexistinggroupof
groupaddressedSounder/Beacons,seesectionxongroupaddressing.
Thesearchfornewdevicesfeatureisconductedasfollows:
a. Usethearrowkeysandscrolldowntosearchfornewdevicesandpressenter.
Thesystemwillscanallunusedaddressesstartingatthelowestuntilanewdeviceisfound.
b. Onceanewdevicehasbeenfoundusethe+/-keysandleftrightarrowkeystoenteranameandzone
number,scrolldownto ADDandpressenter,orSKIP ifyoudonotwishtoaddthenewdevice. The
namecanbealphanumericwithamaximumof12characters,includingspaces.
c. Thesearchwillcontinueuntilallunusedaddressesarechecked.Whenfinishedwilldisplaythe
followingtext“NOFURTHERDEVICESFOUND”.ScrolldowntoENDandpressenter.
d. Thescancanbefinishedatanytimebypressingmenu.
Manuallyenterthetimeanddate,thiswillautomaticallyupdateallotherdisplaysconnectedtothesystem..
Displayssoftwareversion
Thegasdetectionfeatureallowstheusertoscrollthroughallofthegasdetectorsensorsconnectedviewingthe
currentgasconcentration. Additionallythecalibrationmode(CAL MODE)canbeturnedonallowingcalibration
ofthegassensorswithoutanycauseandeffectsoroutputsoperating. Thefiredetectionremainsfully
operationalduringCAL MODE.Ifthecalibrationisinterrupted,duetoanalarm,pre-alarmetc..,theuser
returntotheGasDetectionmenuandturnoffthecalibrationmode.
Viewthegassensorsconcentrationasfollows:
a. Usethearrowkeysandscrolltogasdetectionandpressenter.
b. Usingthe+/-keysselectaloopwithgassensorsconnected. Thefirstofupto10sensorspermittedper
loopwillbedisplayed.
c. Presstherightarrowkeytomoveovertothesensornumber.Usethe+/-keystochangesensor
number.
d. Repeatc.,above,toviewallgassensorsfitted,upto10perloop.
Calibratethegassensorsasfollow:
e. Usethedownarrowkeyandgodownto“CHANGECAL MODE”.Usethe+/-keystoturnthecalmode
onoroff.Enteruserlevel2passwordandpressentertwice.Whenincalibrationmodethe light
willbeilluminatedindicatingallgassensorsareisolated.
f. Oncecalibrationiscompleteturncalmodeoffasstatedabove.Checkthatthe lamponthe
Display ANDthe lampontheLoopcardsarenotilluminated. Turningthesystemoffandthenback
onagainwillensurenogassensorsareleftisolated.
MUST
ISOL
ISOL
ISOL
10:51 05/06/08 GASDETECTION USER1
LOOP:1 SENSOR:1 CAL MODE:OFF
HYC#1E.RM
CONCENTRATION:0%LEL
CHANGECAL MODE:OFF
ED816A AddressableFireandgasdetectionInstallationmanual8-9-08Rev-a