Instruction manual
-23-
Operatinginstructions-systemsetup
3.MAINMENU>SYSTEMSETUP
MAINMENU>SYSTEMSETUP >CALIBRATEGASDETECTORS
MAINMENU>SYSTEMSETUP >WALKTHROUGHTEST
MAINMENU>SYSTEMSETUP >SOUNDERBEACONTEST
Useraccesslevel3isrequired. Afterenteringthepasswordpress“ENTER”andthemainmenuwillbe
displayed,press“ENTER”againforsetup. Thefollowingscreenwillbedisplayed:
Seeitem5,page24.
ThewalkthroughtestfeatureallowsthecommissioningEngineertotesteachdetectorinturneitherbyloopor
zonewithoutthealarmsoranycauseandeffectsoperating. Attheendofthetesttheusercanscrollthrougha
listofalldevicesthatrespondedandintheordertheyweretested. Thewalkthroughisolatesalloutputsofthe
chosenzoneorloop. Thetestmustbeendedbypressingmenuorenterwhenprompted.Ifthetestis
interrupted,duetoanalarm,pre-alarmetc..,theuser returntothetestmenuandendthepreviously
startedtestatthesamedisplayasinitiallyusedtostartthetest. Thewalkthroughtestisconductedasfollows:
a. Usethearrowkeysandscrolldownto“WALK THROUGH TEST”andpressenter.
b. Usingthe+/-keyschoosethelooptobetestedorpresstherightarrowkeytochooseazonetobe
tested.Scrolldownto“OK”andpress“ENTER”. The“TEST”lightshouldnowbeilluminated.
c. Testeachdetectorinturn.Oncethedevicehasactivateditsalarmlightwillilluminateandyoucanmove
ontothenextdevice.
d. Onceyouhavetestedalldevicesensurealldevicesarenolongerinalarm/pre-alarm pressing
enter. Thecontrolpanelwillindicatehowmanydeviceshavebeentestedanddisplaythedetailsoneat
atime.Scrollthroughtested devicesusingtheup/downarrowkeys.Oncefinishedwiththeinformation
pressmenutoreturntothepreviousscreen.Beforestartinganothertestwaitatleast1minute.If
finishedpressmenuagainuntilthemainscreenisdisplayed.
e. Checkthatthe“TEST”lampontheDisplay ANDthe“ISOL”lampontheLoopcardsarenotilluminated.
Turningthesystemoffandthenbackonagainwillensurenozonesorloopsareleftisolated.
Smokedetectorsonlyrequireasingle,shortburstoftestsmokewiththecanisterheldatleast60cmawayor,
preferably,useatestsmokedispenser.Overexposuretotestsmokewillcoatthesensorandreduceworking
life.Itwillrequirecleaningbyasuitablytrainedperson.
Thesounder/beacontestfeatureallowsthecommissioningEngineertotesteachloopsounder,beaconor
soundercontrolmoduleinturn.Eachdevicecanbeoperatedforasetperiodoftimeadjustablefrom30to
240S. Thesounder/beacontestisconductedasfollows:
a. Usethearrowkeysandscrolldownto“WALK THROUGH TEST”andpress“ENTER”.
b. Usingthe+/-keyschoosethelooptobetestedorpresstherightarrowkeytochooseazonetobe
tested.Scrolldownandadjustthetimeasrequired.Scrolldownto”OK”andpress“ENTER”.
c. Eachsounderandbeaconwillbetestedinorderstartingatthelowestaddress.
d. Movetoeachdevicelocationandensurecorrectoperation.Oncealldeviceshavebeentestedpress
menuandstartanothertestorpressmenuagainuntilthemainscreenisdisplayed.
Itisimportanttonotethatthesounder/beacontestwilltesteverysounderandbeaconontheloop/zone
regardlessofwhetherthesystemhasbeenconfiguredtooperatethem. Thereforeitisvitalseparatetestsare
conductedtestingeveryaspectofthecauseandeffectmatrixensuringalldevicesoperateandwithcorrect
tonesetc..
MUST
before
Itisimportanttorememberthatthewalkthroughtestisatoolforthecommissioningengineertoensureall
devicesareincorrectlocationsandarethecorrecttype.WalkthroughtestdoesNOTtestanyoutputfunctions
andcauseandeffects,thereforeitisvitalseparatetestsareconductedtestingeveryaspectofthecauseand
effectmatrixandoutputfunctions.Input/Outputmodulescannotbetestedwiththewalkthroughtest.
10:51 05/06/08 SYSTEMSETUP
1.CALIBRATEGASDETECTORS
2.WALKTHROUGHTEST
3.SOUNDER/BEACONTEST
4.SEARCHFORNEWDEVICES
5.
6.
7.SETTIME ANDDATE
ED816A AddressableFireandgasdetectionInstallationmanual8-9-08Rev-a