Section8-Operatinginstructions
ACCESSLEVELS
SWITCHON/REBOOTSCREEN
TheEuropeanstandardEN54-2requiresaccesstothecontrolequipmenttobesplitinto4levels. Thecontrol
unitcompliesthroughtheuseofpasswords.Inordertomeettheserequirementsthecontrolunitdoorshould
notbelocked.
TheED700A andED816A systemsusethefollowingmethodofaccesscontrol:
Nopasswordrequired,allowingaccessbythegeneralpublic,orpersonshavingageneralresponsibilityfor
safetysupervision,whomightbeexpectedtoinvestigateandinitiallyrespondtoanalarmorfaultwarning.
Systempasswordisfactorysetas“AAAAAA”,allowingaccessbypersonshavingaspecificresponsibilityfor
safety,andwhoaretrainedandauthorizedtooperatethecontrolunitinthefollowingconditions:
1. Quiescentcondition;
2. Alarmcondition;
3. Faultcondition;
4. Disabled/isolatedcondition;
5. Testcondition.
Systempasswordisfactorysetas“BBBBBB”,allowingaccessbypersonswhoaretrainedandauthorizedto:
1. Re-configurethesitespecificdataheldwithinthecontrolunitandequipmentconnectedtoit.
2. Maintainthesystem.
ConnectiontoPCandtheuseofFireconfigsoftwareisrequired,allowingaccessbypersonstrainedtore-
configurethesystem.
Atswitchonoraftersystemrebootthefollowingscreenwillbedisplayed:
Eachloopcardfittedshouldbelistedasresponding.Eachdisplay/repeaterhasadifferentID,setviadip
switches.NotworepeatersshouldhavethesameID.
Pressthemenukeyandthefollowingscreenwillbedisplayed:
Thisisthenormallydisplayedscreen. Thetextinthetoprightcan,atcommissioning,bechangedtosuiteach
application.
Accesslevel1
Accesslevel2
Accesslevel3
Accesslevel4
ED720SYSTEMCHECKINGFORLOOP CARDS:
1.RESPONDING 5.
2.RESPONDING 6.
3. 7.
4. 8.
THISDISPLAY ID:RACK0
10:51 05/06/08 ELECTRONICDEVICES
NOOFDETECTORSIN ALARM:0IN0ZONES
PRE ALARMS0FAULTS0ISOL ZONES0