Instruction manual
-17-
CauseandEffectMatrix-continued
WhenchoosingInput/OutputandOutputmodulesas
outputdevicestheoutputbitdropdownboxappears,
allowingthecommissioningengineertochoosewhich
outputbitsaresetandhencetheRelaytobeswitched.
Pleasenoteoutputbitsarereferredtoasoutput1,2and3
inFireConfigbutasoutputbits0,1and2in Apollo’sliterature.
Refertothe Apollodatasheetsforindividualmodule
types,belowarethemostcommonexamples:
MainsSwitchingInputOutputunit
0 relaydrive 1
1 notused 2
2 notused 3
3channelInputOutputunit
0 channel1relay 1
1 channel2relay 2
2 channel3relay 3
Whenchoosingdelayedoutputinthe“effect”
dropdownboxitispossibletosetupupto8
delayedeffects. The8delayedeffectscanbe
calledasmanytimesasrequiredbydifferent
causeandeffectentries,remembering50
entriesisthemaximumnumberofcauseand
effectsallowed.
The“configuredelayedoutputs”buttonisat
thebottomofthemaincauseandeffects
pageandbringsupthedialogueboxshown.
Delayscanbesetanywherebetween1and
600seconds.
Itisimportanttoensureallfire/gas
detectionstandardsarenotinfringedwhen
addingdelays.E.g.EN54-2stipulateswhat
canandcannotbedelayedwhenoutputsare
connectedto“firealarmroutingequipment”.
Itispossibletooverridedelaysatanystageduringnormaloperationbychoosingitem6(delayedoutputs)from
themainsystemmenu.Itshouldalsoberememberedthat,fromwithinthecauseandeffectmatrix,adedicated
andsuitablylabelledcallpointcouldbeassignedthesame8outputsbutwithoutdelaystherebygivinganeasy
methodtooverridethedelays. Additionallypressingthe“EVAC”buttonoranycallpointnotassignedazone
willoperatetheevacuatecommandandalllooppoweredsounders,beacons,sounderscircuitsandImmediate
Alarm,Pre-AlarmandDelayedoutputrelayswilloperate.
ApolloInputOutputmodulesandOutputmodules
Outputbit Action FireConfigOutput
Outputbit Action FireConfigOutput
DelayedOutput
ED816A AddressableFireandgasdetectionInstallationmanual8-9-08Rev-a