Instruction manual

-15-
CauseandEffectMatrix-continued
AddingCauseandEffectsentries
“CauseandEffect” “addEntry”
“inputtype”
“Device”
“Zone”
“Loop”
“Cause”
“Coincidence”
I/OunitLatching I/OunitNon-Latching.
1. Click andthen .
2. Chooseanamefortheentry.
3. Selectthe .
isanydetector,inputmodule,zone
monitororswitchmonitoronanyloop.
isanyofthe32zonesandalsoeitherofthe
2builtinconventionalzones.
isanyoftheloopsattachedtothesystem
onlyloop1and2applyfortheED816A.
4. Select .Causecanbepre-alarm,alarm
orfault.
IfZonewaschosenforinputtypeanextracause
choicebecomesavailable.
detectionisavailablebetweenany2zones.
Intheeventofthe2zoneschosenbothbeingin
thealarmconditionthentheeffectwillbeactioned.
IfDevicewaschosenforinputtypeandthedeviceisanI/Omodule,2extracausechoicesbecome
available. and
Apollomanufacture3mainI/Omoduleswiththefollowinginputs:
MainsswitchingI/O 0 1 statusofmonitoredswitch
1 2 notused
2 3 notused
InputOutputUnit 0 1 statusofmonitoredswitch
1 2 statusofoptoinput
2 3 notused
3ChannelInputOutputUnit 0 1 statusofmonitoredswitch1
1 2 statusofmonitoredswitch2
2 3 statusofmonitoredswitch3
Whilstthemonitoredswitchisopennoeffectwilloccur,oncetheswitchclosesthechoseneffecttakes
place.
Whenchoosing“I/OunitLatching”theeffectwillremainuntilRESET hasbeenpressed,any
effectcanbechosenfromthedropdownbox.
WhenChoosing“I/OunitNon-Latching”theeffectwillremainforonlyaslongastheinputisset.Only
LoopDevicescanbechoseninthe“Effect”dropdownbox.Whenoperatingaloopoutputdeviceonly
onenon-latchingcausecanbeassignedtoit.
5. SelectOutputtypeinthe“effect”dialoguebox,whichcanbe AuxRelay,Sounder,LoopDeviceor
DelayedOutput.
I/Omodule inputbits FireConfiginput use