Specifications
Provide an external outlet or hood outlet to collect
the oven exhaust air. It is recommended also to avoid
humid air and cooking smells inside the kitchen.
The pipe of evacuation of the air must be dimensioned
in order to guarantee 150 m
3
/h airow and an outlet
area of at least 70 cm
2
.
Install an external extractor fan when:
»
The pipe ( 100) is more than 1.5 m in length
»
There is more than one 90° bend on the pipe
It is recommended to avoid traps in the air outlet pipe
in order to prevent deposits of condensation.
Provide the air outlet pipe with a device in order to
prevent any cold air back ow and prevent the entrance
of any obstruction as leaves or insects.
It is recommended to avoid traps in the air outlet pipe
in order to prevent deposits of condensation.
It is necessary that the drain connection point is
equipped with a siphon device.
Leave a minimum of 300 mm height between the oven
drain outlet and the drain connection point.
The drain pipe is not supplied with the Combination
Oven.
Technical symbols legend at page 7
Install the air conveyor (available as accessory).
250 mm
9 7/8
"
D
CWI
EI
AO