Specifications

Electroswitch 180 King Avenue Weymouth, MA 02188 TEL: (781) 335-5200 FAX: (781) 335-4253 www.electroswitch.com
67
E
CIM
CONTROL INDICATOR MODULE
2. Trip Coil Monitor (red) LED:
Indicates the continuity (tests for an open
circuit) of the breaker trip coil. The CIM
electronics continuously check the continuity
of either a single, dual, or ganged single
trip coils (a field programmable dip switch
located within the CIM selects what type
of breaker coil is to be monitored). If the
LED is “ON” the coil is satisfactory. If the
LED is “OFF” the coil has failed or the
breaker is tripped.
1. Breaker Open (green) LED: Indicates the
physical state of the breaker (either open or
closed). In addition this LED provides visual
indication of which device caused the trip. A
steady "ON" LED indicates a trip signal from any
protective relay device. A rapid flashing LED
indicates a trip signal from SCADA. A slow flash-
ing LED indicates a trip signal from the manual
control switch located on the CIM.
Monitors/Indicators:
The CIM provides visual indication of the functions monitored by the unit. These include breaker
contact status (opened/closed), breaker coil continuity, and operational state of both the Reclose
function and the interface to SCADA. The following describes each of the four indicator LEDs
located on the front panel of the CIM.
1.
3.
2.
4.
Reclose Enable/
Disable Switch
SCADA Enable/
Disable Switch
Manual Fail-
Safe Switch
Panel
Locking Device
Ordering Information
Model No. Description
64
2-100 Standard Parallel SCADA CIM - Horizontal Mounting
642-900 Standard Parallel SCADA CIM - Vertical Mounting
642-905 Modified Standard Parallel SCADA CIM - Vertical Mounting -
SCADA Trip Disables Reclose
642-107 Modified Standard Parallel SCADA CIM - Horizontal Mounting - Trip Coil LED
Shows Steady On When in Close and Flashes when Trip Coil is Bad
642-108 Modified Standard Parallel SCADA CIM - Horizontal Mounting -
Modified Software and Hardware to Control a Circuit Switcher
672-100 Standard Serial Modbus SCADA CIM - Horizontal Mounting
672-900 Standard Serial Modbus SCADA CIM - Vertical Mounting
672-106 Standard Serial DNP3.0 SCADA CIM - Horizontal Mounting
672-906 Standard Serial DNP3.0 SCADA CIM - Vertical Mounting
Specifications
Input Voltage - 38.4 -140VDC
Output Current – Trip: 20A for 0.5 Sec
0.5A Continuous
Close/Reclose:
30A for 1 Sec
1.5A Continuous
Control Power Requirements - 38.4 - 140VDC @ 100 Milliamps
Communications - 9 Pin Mini DIN Connector
Operating Temperature range: -20˚C to +55˚C
RS-485, 1200, 2400, 4800, and 9600 Baud (consult factory for other baud rates)
Parallel Interface: 38.4 - 140VDC Std, 24VDC Optional
Meets IEEE C37.90.1 and C37.90.2
3. Reclose Out (amber) LED:
If the LED is “ON”
the reclose relay is disabled (out).
If the LED is “OFF”
the reclose relay is enabled (in).
4. SCADA Out (amber) LED:
If the LED is “ON”
the SCADA interface is disabled (out).
If the LED is “OFF”
the SCADA interface is enabled (in).