User manual
e
Electro Industries/GaugeTech
Doc #: E113-7-07 V1.04 2-4
configuration port number.
NOTE: Be sure to include a space between the IP address and 9999.
2.8:
Configuration
Parameters
The screen, below, shows the basic configuration parameters.
telnet x.x.x.x 9999
Hardware: Ethernet Autodetect
IP addr - 0.0.0.0/DHCP/AutoIP, no gateway set
DHCP device name : not set
***************** Security *****************
Telnet setup is enabled
TFTP download is enabled
Port 77FEh is enabled
Web Server is enabled
Enhanced password is disabled
***************** Channel 1 *****************
Baudrate 57600, I/F Mode 4C, Flow 00
Port 10001
Remote IP Adr: --- none ---, Port 00000
Connect Mode : C0 Disconn Mode: 00
Flush Mode : 00
***************** Channel 2 *****************
Baudrate 9600, I/F Mode 4C, Flow 00
Port 10002
Remote IP Adr: --- none ---, Port 00000
Connect Mode : C0 Disconn Mode: 00
Flush Mode : 00
Change Setup : 0 Server configuration
1 Channel 1 configuration
2 Channel 2 configuration
6 Security
7 Factory defaults
8 Exit without save
9 Save and exit Your choice ?