User manual
eElectro Industries/GaugeTech Doc # E113-7-03-1.18 2-15
2.10: Reset and Modem Commands2.10: Reset and Modem Commands
n
Use this command to change the Programmable Reset and Hang-up Times.
• Type HR[Enter]. The following screen appears.
------------------------------------------------------
RESET & HANG-UP COMMANDS
R : Reset Now
RH : Program Hang-up Time
RT : Program Reset Time
------------------------------------------------------
• Type R[Enter] to reset the unit right away.
• Type RH[Enter] to change the Programmable Hang-up Time. Choose a Hang-up Time from
the following: 0 = No Hang-up, 1 = 5 minutes, 2 = 10 minutes.
For example: Type RH1[Enter] for a 5 minute hang-up.
• Type RT[Enter] to change the Programmable Reset Time. Choose a Reset Time from the
following: 0 = No Reset, 1 = 5 minutes, 2 = 10 minutes.
For example: Type RT2[Enter] for a 10 minute reset.
• To check changes made by the RH and RT commands, Type HU[Enter] (Unit Status command;
see section 2.9). Changes will be effective after the unit is reset.
• RH command is useful when the unit is connected to a phone line. If no activity is detected for
5 or 10 minutes, SM1-16 will disconnect the phone line. This will save costly phone bills.
• If you do not want SM1-16 to disconnect automatically, use the RH[Enter] command for No
Hang-up. The RT command is similar but is used when the unit is not on a phone line.
NOTE: In the previous runtime version (v35), the default was NO-RESET and NO-HANGUP.
In this runtime version (v36), the default settings have been changed to 10-minute RESET and
10-minute HANGUP.
2.11: Site ID2.11: Site ID
n
Use the Site ID command to name the location of the Substation Multiplexor. A maximum of 14
characters is allowed.
• Type SIsite_name[Enter], where site_name is a string of up to 14 characters.
• To confirm this change, Type HU[Enter] (the Unit Status command; see section 2.9).