User manual
eElectro Industries/GaugeTech Doc # E113-7-03-1.18 2-8
2.5: Command Mode2.5: Command Mode
n
To enter Command Mode from Throughput Mode, send the following escape string:
• [2-second pause]%%%[2-second pause] (or $$$,###,@@@,!!!)
• After the last 2-second pause, type H[Enter].
v Note: The “%” keystrokes must be made less than two seconds apart.
n
BE SURE TO USE ALL CAPITAL LETTERS WHEN SENDING COMMANDS TO THE
MULTIPLEXOR; THE UNIT ONLY RECOGNIZES CAPITAL LETTERS.
n
To begin, type H[Enter]. The following Command Menu appears:
--------------------------------------------
EIG SM Command Mode Commands
H : Display This Menu
HP : Display Port Program Commands
HS : Display Port Status
HM : Display Modem Program Commands
HU : Display Unit Status
HR : Display Reset & Hang-up Commands
SI : Program Site ID
GT : Go to Throughput Mode
GB : Go to Boot Mode
GM : Go to Mode Selection
GS : Select the Escape Sequence
PW : Password Protection
EIG : Electro Industries
--------------------------------------------
n
Commands are listed on the left. Type any command and press Enter. Type H[Enter] at anytime to
access this menu. See the following sections for details about each command.
n
In the previous runtime version (v35), all commands were available when the unit was in command
mode. There are two types of commands; one type can change the programmable settings in the
Flash, the other type cannot change the settings in Flash.
In this runtime version (v36), after Powerup or Reset, the commands that change the data in
the Flash will be disabled.
For example, if you type PS03[Enter], the unit will respond ‘Type H[Enter] to enable this command’.
• To Enable these commands, enter the H command first. Enter H[Enter]. Then enter
PS09[Enter]. OK will appear on your screen to confirm that the command is enabled.
• To Disable these commands, enter the HU command. The HU command will disable all
commands that can change the data in Flash.