3.
Multi protective function
3.1 Anti-freezing protecting control: 
When the ambient temperature is low while in Cooling Mode, the compressor and water 
motor will stop working if the copper coil temperature reaches <2℃  for over 20 seconds. 
When  the  copper  coil  temperature  increases  to  >8℃,  the  protection  will  be  stopped 
automatically.   
3.2、Water-full protection: 
When the water level in the internal water tank is surpassing the maximum level, the 
unit will alert automatically and “P2” will flash on the LCD screen. Please discharge 
water in the machine according to page 12 - “Water Drainage” 
3.3 Compressor delay-protection   
Except  for  the  first  power-on,  (or  when  changing  from  Cooling  to  Heating  mode)  the 
compressor can start instantly.   
The compressor also runs under a 3 minute delay protection function.   
3.4 Compressor protection 
In cooling, dehumidifying and heating mode, if the temperature difference between 
the coil temperature and room temperature is less than 3℃, for more than 30 
minutes, the machine will enter ‘no refrigerant’ compressor protection mode.   
The compressor and water spring motor will stop working. 
The up fan runs at low speed and the down fan stops running   
“E3” will appear on the LCD screen. 
Press any key on the control panel; the background light will illuminate for 10 seconds. 