Specification Sheet
45 
Model 
eiQ-SSRFC48K-V4 
eiQ-SSRFC60K-V4 
Indoor Rated voltage and frequency (Ph-V-Hz) 
N/A 
N/A 
Outdoor Rated voltage and frequency (Ph-V-Hz) 
380~415/3/50 
380~415/3/50 
Indoor Fuse Required 
N/A 
N/A 
Outdoor Fuse Required 
20A 
20A 
Mode 
Cooling 
Heating 
Cooling 
Heating 
Rated capacity (KW) 
14.0 (7.0-15.5) 
15.2 (8.0-16.0) 
16.0(7.5-17.0) 
16.8 (8.5-17.5) 
Power input (W) 
4950 (1100-5800) 
4920 (1200-6000) 
5900 (1400-6300) 
5460 (1500-6500) 
Current input (A) 
2.8-14.6 
3.0-15.0 
3.5-15.8 
3.7-16.3 
SEER/SCOP(W/W) 
6.1 / A++ 
4.0 / A+ 
6.1 / A++ 
4.0 / A+ 
Nominal load (kW) 
14.000 
11.500 
16.000 
12.000 
Balance point temperature heating (
o
C) 
-
-7 
-
-7 
Min. outdoor operating temperature (
o
C) 
-15 
-15 
-15 
-15 
Thermostat-off mode (W) 
101 
23.9 
128 
23.6 
Standby mode (W) 
3
3
Off mode (W) 
3
3
Annual consumption (kW) 
795 
3723 
911 
4046 
Copper Pipe Type length 
-
-
Liquid side / Gas side (mm/inch) 
Φ9.52/Φ15.88 
Φ9.52/Φ15.88 
Max. refrigerant pipe length 
65 
65 
Max. elevation 
30 
30 
Interconnecting Cable 
4 x 2.5mm
2
4 x 2.5mm
2
Moisture Removal (L/h) 
5.08 
7.96 
Indoor
Air Flow (m
3
/h) 
1900 
2000 
Body Dimensions (L*W*H) (mm) 
840x285x840 
840x285x840 
Panel Dimensions (L*W*H) (mm) 
950x50x950 
950x50x950 
Body Packaging (L*W*H (mm) 
920x310x920 
920x310x920 
Panel Packaging (L*W*H (mm) 
1030x100x1030 
1030x100x1030 
Body Net / Gross weight (Kg) 
29/34 
29/34 
Panel Net / Gross weight (Kg) 
6.5/9.5 
6.5/9.5 
Noise – Sound pressure level (dB/A) 
45-52 
45-52 
Noise – Sound power level (dB/A) 
56-63 
56-63 
Outdoor
Dimension (L*W*H) (mm) 
1014x1430x450 
1014x1430x450 
Packaging (L*W*H) (mm) 
1095x485x1545 
1095x485x1545 
Net / Gross Weight (Kg) 
109/123.6 
112/126.6 
Noise – Sound pressure level (dB/A) 
58 
58 
Noise – Sound power level (dB/A) 
70 
70 
Refrigerant type/weight 
R32 / 3800g 
R32 / 3800g 
Defrost mode 
Automatic defrosting 
Automatic defrosting 
Applicable climate types 
Cooling (-15
o
C – 50
o
C) 
Heating(-15
o
C – 30
o
C) 
Cooling (-15
o
C – 50
o
C) 
Heating(-15
o
C – 30
o
C) 
Due to continuous product development process specification may change. 
These units contain a gas governed by F-Gas regulations. The gas must be handled by qualified F-Gas engineers. 