OPERATION
The recommended humidity for a standard room is within the range of 50% to 70%, provided no
special requirements are made.
Although the desired humidity can be set as low as 10%, lower settings will act as a continuous
mode, as they are unlikely to be achievable in the UK.
WATER TANK FULL
The dehumidifier will display the TANK FULL symbol, bleep, and enter standby mode when the water tank is
full. To resume operation the water tank should be emptied and reinserted into the unit.
If this happens when the unit is set up with continuous drainage, it indicates either a blockage of the drain
pipe, or that the pipe is not going downhill. Check the route of the drain pipe to resolve the error.
AUTO DEFROST
When frost builds up on the evaporator coils, the compressor will cycle off and the unit will go in to defrost
mode. Following completion of the defrost mode, the unit will return to the previously operating settings.
DEFROSTING MODE
DESCRIPTION
Automatic defrosting
Sensor at normal state
This mode is entered when the
compressor runs constantly for 30
min and the coil temperature is
-1.
In defrost mode the compressor stops
running, the fan continues running
and the defrosting light is on.
Timing defrosting
The unit defrosts for 8 minutes
Note: When the ambient temperature is low, the appliance will enter defrost mode more often
HUMIDITY CONTROL
When the unit reaches the desired humidity set, both the fan and compressor will shut down; and when
the humidity of the room is above the desired level both fan and compressor will operate.
If the room humidity displayed appears to be incorrect, it can be adjusted by following the below:
1. In standby mode, press and hold the TIMER Button for over 10 seconds.
2. Both the Set Humidity and Current Humidity symbol will flicker and the humidity display will show
the current humidity
3. Use the UP and DOWN buttons to adjust the humidity reading.
FAULT PROTECTION
The intelligent logic within the unit will monitor the performance of the refrigerant circuit. If after 10
minutes the temperature of the cold coil within the unit has not reduced sufficiently, the unit will enter
standby mode and “PRESSURE HOLDING” will be displayed on the control panel. The unit will not operate
until the fault has being rectified.