PRODUCT DATA SHEET
SM DLF 1-A.1 GB
2.2 DLF 35 DCI
Model Indoor Unit DLF 35 DCI
Model Outdoor Unit ONG3-35 DCI
Installation method of Pipe DUCTED
Characteristics Units Cooling Heating
Capacity (1)
Btu/hr 11940 (4780-14670) 14670 (5100-19790)
kW 3.5 (1.40-4.30) 4.3 (1.50-5.80)
Power input (1) kW 0.95 1.16
EER (Cooling) or COP (Heating) (1) W/W 3.67 3.62
Energy efficiency class A A
Power supply V/Ph/Hz 220-240/1/50
Rated current A 3.67 4.8
Starting current A 10.5
Circuit breaker rating A 16
INDOOR
Fan type & quantity Centrifugal & 2
Fan speeds H/ M/ L RPM 980/860/730
Air flow (2) H/ M/ L m³/hr 650/580/490
External static pressure Min-Max Pa 0-30
Sound power level (3) H/ M/ L dB(A) 53/49/45
Sound pressure level (4) H/ M/ L dB(A) 31/27/24
Moisture removal L/hr 1.0
Condensate drain tube I.D mm 19
Dimensions WxHxD mm 200x750x630
Weight kg 20
Package dimensions WxHxD mm 885x695x226
Packaged weight kg 23
Units per pallet Units 14
Stacking height Units 7
OUTDOOR
Refrigerant control Electronic Expansion Valve
Compressor type, model DC Inverter single rotary
Fan type & quantity Axial & 1
Air flow H / L m³/hr 1780
Sound power level H / L dB(A) 62
Sound pressure level (4) H / L dB(A) 52
Dimensions WxHxD mm 795x610x290
Weight kg 38
Package dimensions WxHxD mm
945x655x395
Packaged weight kg
43
Units per pallet Units 9
Stacking height Units 3
Refrigerant type R410A
Refrigerant charge (standard connecting
tubing length)
kg 1.2
Additional charge per 1 meter g/m No need
Connections
between units
Liquid line In. 1/4”
Suction line In. 3/8”
Max. tubing length m. 20
Max. height difference m. 15
Operation control type I.R Remote control
Heating elements kW
Others
(1) Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
(2) Airflow without external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1-meter distance from unit.
CONTENT