CONTROL SYSTEM
SM DLF 1-A.1 GB
13.3.5 ODU Model Dependent Parameters ( 35V12 )
#
Outdoor Model
Parameter
A
Single
DCI-25
B
Single
DCI-35
C
Single
DCI-50
D
Single
DCI 60
1 MinFreqC 30 33 20 20
2 MaxFreqC 64 80 85 95
3 MinFreqH 30 35 20 26
4 MaxFreqH 81 93 95 94
5 NormAccel 11 1 1
6 NormDecel 11 1 1
7 Step1Freq 60 60 60 60
8 Step2Freq 70 70 70 70
9 Step3Freq 90 90 90 90
10 OFVL 20 20 20 20
11 OFLOWC 55 55 60 55
12 OFMEDC 70 70 76 70
13 OFMAXC 83 83 92 79
14 OFLOWH 55 55 60 55
15 OFMEDH 70 70 83 70
16 OFMAXH 83 83 100 79
17 OFANTESTMODEC 83 83 92 83
18 OFANTESTMODEH 83 83 100 83
19 OFDelTestMode 20 20 28 28
20 CTTOH1 94 94 94 94
21 CTTOH2 98 98 98 98
22 CTTOH3 102 102 102 102
23 CTTOH4 105 105 105 105
24 CCROC1 7.1 7.1 10 11.4
25 CCROC2 7.5 7.5 10.5 11.8
26 CCROC3 7.9 7.9 10.8 12.2
27 CCROC4 8.3 8.3 11.2 12.6
28 DEICT1 60 60 60 60
29 DEICT2 36 36 36 36
30 DEICT3 66 6 6
31 ProtFreqLimit 60 60 60 60
32 EEVDecierOpen 180 180 100 180
33 OptimDeicFreq 90 90 90 90
34 EEVMinOperOpenC
50 50 50 80
35 EEVMaxOperOpenC 380 380 380 380
36 EEVMinOperOpenH 50 50 50 60
37 EEVMaxOperOpenH 300 300 380 300
38 EEVNormRate 33 33 33 33
39 EEVHighRate 12 12 12 12
40 EEVMaxOpen 500 500 500 500
41 OFLowFreqC 45 45 40 35
42 OFMedFreqC 57 57 70 55
43 OFLowFreqH 45 45 40 40
44 OFMedFreqH 57 57 86 60
45 HeaterDisableFlag 00 0 0
46 DeiceFreqChRV 00 0 0
47 OATRefC 35 35 35 35
48 SUCT Enable 00 0 0
49 HST Enable 00 1 1
50 OAT Enable 11 1 1
51 OATRefH 77 7 7
52 MinTargCTTC 30 30 30 30
53 MaxTargCTTC 95 95 95 90
54 MinTargCTTH 40 40 40 45
55 MaxTargCTTH 95 95 95 90
56 DST 88 8 8
57 DSTF 12 12 12 12
58 OATLimitC 24 24 28 28
59 OATLimit1H 66 6 6
60 OATLimit2H 15 15 15 15
61 MaxFreqAsOATC 50 50 64 85
62 MaxFreqAsOAT1H 65 75 85 80
63 MaxFreqAsOAT2H 60 60 60 60