Service manual
13-20
CONTROL SYSTEM
SM DLF 1-A.1 GB
13.2.3 Unit Operation in Test Mode
In test mode, the unit will operate in fixed settings according to the indoor fan speed setting:
Indoor FAN Speed Setting Unit Setting
Low Minimum Capacity Setting
Turbo Nominal Capacity Setting
Auto Maximum Capacity Setting
During test mode, protections are disabled, except for stop compressor status.
13.3 Parameters
13.3.1 General Parameters for all models
# Name Values(Factory Setting)
1 CVStep 0
2 Cool2Heat 3
3 Heat2Cool 3
4 ICTDef1 8
5 ICTDef2 6
6 ICTDef3 4
7 ICTDef4 2
8 ICTDef5 0
9 ICTDef6 -2
10 ICTDeltaDef1 1
11 ICTDeltaDef2 -1
12 ICTDeltaOH1 -1
13 ICTDeltaOH2 1
14 FLTRTime 1023
15 PITconst 30
16 STARTTIMETURBOH 10
17 IFANOffTimeDry 3
18 IFANOnTimeDry 1
19 ICTLowLimitDry 10
20 ICTHighLimitDry 12
21 ExtraNLOADDry 20
22 IFANMAXTimeH 150
23 IFANOffTimeH 4
24 IFANOnTimeH 3
25 IFANTimeHeat2STBY 30
26 MAXTURBOTIMEF 30
27 MAXTURBOTIMEC 30
28 MAXTURBOTIMEH 30