Service manual

13-16
CONTROL SYSTEM
SM DLF 1-A.1 GB
Presence Detector/Power Shedding Selection
Select the functions of dry contact PD/PS by setting the Dip switch J9
Selection J9
Presence Detector OFF
Power Shedding ON
Installation of height compensation settings (By installer)
The compensation settings according to installation height should be set by using the dip switch J12,
J13 on the controller PCB
Installation Height J12 J13 Installation height
H0 OFF OFF 2.1-2.7m
H1(Factory setting) ON OFF 2.7-3.3m
H2 OFF ON >3.3m
H3 ON ON Reserved
Compensation data according to the installation height
Installation
Height
Speed Compensation for
Heating Mode
Speed Compensation for
other Modes
Temperature compensation
in heating mode
CK DLF CK DLF CK DLF
H0 -50 0 -50 0 42
H1 0 150 0 150 4 2
H2 100 150 100 150 6 2
H3 150 150 150 150 7 2