Service manual
13-9
CONTROL SYSTEM
SM DLF 1-A.1 GB
13.1.16.2 Indoor Coil Defrost Protection — DLF
ICT
Trend
Fast Increasing Increasing No Change Decreasing Fast Decreasing
< -2 SC SC SC SC SC
[-2, 0) D1 D1 D2 D2 D2
[0, 2) SR SR D1 D2 D2
[2, 4) SR SR SR D1 D2
[4, 6) Norm Norm SR SR D1
[6, 8] Norm Norm Norm SR SR
> 8 Norm
13.1.16.3 Indoor Coil Overheating Protection
ICT
ICT Trend
Fast Decreasing Decreasing No Change Increasing Fast Increasing
>62 SC SC SC SC SC
[60, 62) D1 D1 D2 D2 D2
[55, 60) SR SR D1 D2 D2
[52, 55) SR SR SR D1 D2
[48, 52) Norm Norm SR SR D1
[45, 48) Norm Norm Norm SR SR
I<45 Norm
13.1.17 Compressor Overheating Protection
13.1.17.1 Compressor Overheating Protection for DCI25/35/50/60/72Z
Compressor temperature can be in one of 5 control zones (4 in protection, and 1 normal),
according to the following chart.
Normal
P1
P2
P3
Sto
p
-Com
p
resso
r
94
98
102
105
CTT
Control Status Compressor Temperature Increases Else
P1 Normal Stop Rise
P2 HzDown 1 Stop Rise
P3 HzDown 2 HzDown 1
Stop Compressor Stop Compressor