Service manual
8-1
ELECTRICAL DATA
SM DLF 1-A.1 GB
8. ELECTRICAL DATA
8.1 Single Phase Units
MODEL DLF 25-35 DLF 50-60 DLF 72
Power Supply
To Indoor To Indoor or Outdoor To Outdoor
1PH – 230V – 50 Hz 1PH – 230V – 50 Hz 1PH – 230V – 50 Hz
Max Current, A 10.5 15 15
Circuit Breaker 16 20 20
Power Supply Wiring No. X
Cross Section mm
2
3 X 1.5 mm
2
3 X 2.5 mm
2
3 X 2.5 mm
2
Interconnecting Cable RC
Model No. X Cross Section
mm
2
4 X 1.5 mm
2
4 X 2.5 mm
2
4 X 2.5 mm
2
NOTE:
Power wiring cord should comply with local lows and electrical regulations requirements.