Service manual
16-45
APPENDIX A
SM DLF 1-A.1 GB
1. Charging set 
2. Vacuum pump 
3. OUTDOOR UNIT 
4. Service valve 
5. Cap 
6. Suction valve 
7. Service valve* 
8. Cap 
9. Liquid valve 
10. INDOOR UNIT 
11. Suction flare connection 
12. Liquid flare connection 
PIPE CONECTIONS TO THE UNIT 
Connecting to the indoor unit 
1.  Align the center of the pipes and 
finger tight the flare nut. 
2. Use the torque wrench to tighten 
the nut firmly. 
Connecting to the outdoor unit 
1.  Align the center of the pipes to the 
valves.
2. Use the torque wrench to tighten 
the valves firmly according to table: 
Tube (Inch)/ 
Torque(N.m) 
1/4 3/8 1/2 5/8 3/4 
Flare Nuts  13-18 40-45 60-65 70-75 80-85 
Valve Cap  13-20 13-20 18-25 18-25 40-50 
Service Port 
Cap
11-13 11-13 11-13 11-13 11-13 
EVACUATION OF PIPES AND INDOOR UNIT 
After connection the unions of the indoor and 
outdoor units, evacuate the air from the tubes 
and from the indoor unit as follows: 
1.  Connect the charging hoses with a push pin 
to the low and high sides of the charging set 
and the service port of the suction and liquid 
valves. Be sure to connect the end of the 
charging hose with the push pin to the service 
port.
2.  Connect the center hose of the charging set 
to a vacuum pump. 
3.  Turn on the power switch of the vacuum 
pump and make sure that the needle in the 
gauge moves from 0MPa (0cm Hg) 
to - 0.1 Mpa (-76cm Hg). Let the pump run for 
fifteen minutes. 
4.  Close the valves of both the low and high 
sides of the charging set and turn off the 
vacuum pump. Note that the needle in the 
gauge should not move after approximately 
five minutes. 
5.  Disconnect the charging hose from the 
vacuum pump and from the service ports of 
the suction and liquid valves. 
6.  Tighten the service port caps from both 
valves, and open them using a hexagonal 
Allen wrench. 
7.  Remove the valve caps from both valves, and 
open them using a hexagonal Allen wrench. 
8.  Remount valve caps onto both of the valves. 
9.  Check for gas leaks from the four unions and 
from the valve caps.
Test with electronic leak detector or with a 
sponge immersed in soapy water for bubbles.
NOTE: For additional charge of various tubing 
lengths, refer to outdoor unit table.
CONTENT










