PRODUCT DATA SHEET
SM DLF 1-A.1 GB
2.4  DLF 60 DCI 
Model Indoor Unit DLF 60 DCI 
Model Outdoor Unit DCI 60
Installation method of Pipe DUCTED
Characteristics Units Cooling Heating
Capacity (1)
Btu/hr 20800 (5120-22860) 22520 (5120-26950)
kW 6.1 (1.50-6.70) 6.6 (1.50-7.90)
Power input (1) kW 1.9 1.7
EER (Cooling) or COP (Heating) (1) W/W 3.25 3.81
Energy efficiency class  A A
Power supply V/Ph/Hz 220-240/1/50
Rated current A 8.2 7.8
Starting current A 15
Circuit breaker rating A 20
INDOOR
Fan type & quantity Centrifugal & 3
Fan speeds H/ M/ L RPM 1170/1050/960
Air flow  (2) H/ M/ L m³/hr 1100/950/880
External static pressure Min-Max Pa 0-40
Sound power level  (3) H/ M/ L dB(A) 59/55/53
Sound pressure level (4) H/ M/ L dB(A) 38/34/32
Moisture removal L/hr 1.7
Condensate drain tube I.D mm 19
Dimensions WxHxD mm 1050x630x200
Weight kg 25
Package dimensions WxHxD mm 1185x695x226
Packaged weight kg 28
Units per pallet Units 14
Stacking height Units 7
OUTDOOR
Refrigerant control Electronic Expansion Valve
Compressor type, model Scroll
Fan type & quantity Axial & 1
Air flow  H / L m³/hr 2860
Sound power level  H / L dB(A) 65
Sound pressure level (4) H / L dB(A) 55
Dimensions WxHxD mm 846x690x302
Weight kg 46
Package dimensions WxHxD mm
990x770x430
Packaged weight kg
50
Units per pallet Units 9
Stacking height Units 3
Refrigerant type R410A
Refrigerant charge (standard connecting 
tubing length)
kg 1.65
Additional charge per 1 meter g/m No need
Connections 
between units
Liquid line In. 1/4”
Suction line In. 1/2”
Max. tubing length  m. 30
Max. height difference m. 15
Operation control type I.R Remote control
Heating elements kW
Others
(1) Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
(2)  Airflow without external static pressure.
(3)  Sound power in ducted units is measured at air discharge.
(4)  Sound pressure level measured at 1-meter distance from unit.