Service manual
12-2
TROUBLESHOOTING        
Revision Y06-02 Service Manual - KN Series
 ATTENTION : check for broken or loose cable lugs first 
NO SYMPTON  PROBABLE CAUSE   CORRECTIVE ACTION 
9. Only indoor fan and 
compressor working. 
Outdoor fan blocked.  - Remove obstructions. 
10.   Only indoor fan 
working. 
-Run capacitor of outdoor 
fan motor faulty. 
-Windings of outdoor fan 
are shorted. 
- Replace capacitor. 
-Replace motor. 
11. No cooling or heating 
takes place, indoor 
and outdoor fans 
working. 
- Overload safety device on 
compressor is cut out (low 
voltage or high 
temperature) 
- Compressor run capacitor 
faulty. 
- Compressor windings are 
shorted. 
- Check for proper voltage, switch off power 
and try 
again after one hour. 
- Replace compressor capacitor. 
- Replace compressor. 
12.No air supply at 
indoor unit, 
compressor 
operates. 
-Indoor fan motor is blocked 
or turns slowly. 
-indoor fan run capacitor 
faulty. 
- motor windings are 
shorted. 
- Check voltage,repair wiring if necessary. 
-Check fan wheel if it is tight enough on 
motor shaft,tighten if necessary. 
-Replace indoor fan motor. 
13. Partial, limited air 
supply at indoor 
indoor unit. 
Lack of refrigerant (will 
accompanied by whisteling 
noise) cause ice forma
tion 
on indoor unit coil in cooling 
mode. 
-Charge the unit after localizing leak. 
14. Water accumulates 
and overflow from 
indoor unit section. 
Drain tube or spout of drain 
pan clogged. 
-Disasemble plastic drain tube from spout of 
indoor unit drain pan. 
15. Water dripping from 
outdoor unit base. 
(in heating mode) 
Water drain outlet is 
clogged. 
-Open outdoor unit cover clean out water 
outlet ,clean the base inside througly. 
16.
Freeze-up of outdoor 
coil in heating mode, 
poor heating effect in 
room, indoor fa
n 
operates. 
-Faulty outdoor thermistor. 
-Faulty control cable. 
- Outdoor temperature is 
too low (below -10°C) 
-Outdoor unit air outlet is 
blocked. 
-Replace thermistor. 
- Repair control cable. 
- Shut unit off, outdoor temp. is below design 
conditions and cannot function properly. 
-Remove obstructions. 
CONTENT