TROUBLESHOOTING
Revision Y06-02Service Manual - KN Series
12. TROUBLESHOOTING
 ELECTRICAL & CONTROL TROUBLESHOOTING 
 ATTENTION : check for broken or loose cable lugs first. 
NO SYMPTON  PROBABLE CAUSE  CORRECTIVE ACTION 
1. The power supply 
indicator (red led) 
doesn’t light up. 
There is no correct voltage 
between the line and 
neutral terminals on main 
P.C.B.
-If the voltage is low repair power supply. 
-If there is no voltage repair general wiring. 
-If there is correct voltage replace main or 
display P.C.B’S 
2. The operating 
indicator (green led) 
does not light up. 
The remote control 
batteries are discharged 
-Replace batteries of the remote control 
3. The operating 
indicator (green led) 
does not light up when 
starting from unit.. 
Check  main P.C.B and 
display P.C.B. 
-Replace P.C.B if necessary. 
4. The indoor fan does 
not function correctly. 
Check  the voltage between 
indoor fan terminals on the 
main P.C.B 
- If there is voltage replace capacitor or 
motor. 
5. The outdoor fan does 
not function correctly. 
Check  the voltage between 
indoor fan terminals on the 
main P.C.B. 
There is voltage between 
outdoor fan terminals on 
the outdoor unit. 
There is no voltage 
between outdoor fan 
terminals on the outdoor 
unit.
- If there is no voltage replace main P.C.B 
- Replace capacitor or motor. 
- Check and repair electrical wiring between 
indoor and outdoor units. 
6. The compressor does 
not start up. 
Check  voltage on 
compressor terminals on 
the outdoor unit. (with 
ampmeter) 
Check if there is correct 
voltage between 
compressor terminals on 
the outdoor unit. 
-If no voltage replace main P.C.B. 
- If low voltage repair power supply. 
-If the voltage corrrect replace capacitor or 
compressor. 
-If there is no voltage repair electrical wiring 
between indoor and outdoor units. 
7. The ref
rigeration 
system does not 
function correctly. 
Check  for leaks or 
restrictions, with 
ampmeter, pressure guage 
or surface thermometer. 
- Repair refrigeration system and charge 
refrigerant if necessary. 
8. No cooling or heating 
only indoor fan works. 
Outdoor fan motor faulty or 
other fault caused, 
compresssor overload 
protection cut out. 
-Replace P.C.B. 
- Outdoor fan blocked remove obstructions. 